5. Function settings (continued)
No.43
Indoor temperature correction
Set the correction for the indoor temperature displayed on the
PZ-62DR-E screen by function
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
43
-
-
-
-
-
-
-
-
-
-
-
-
-
-
No.44
CO
concentration correction
2
CO
concentration displayed on the PZ-62DR-E can be corrected.
2
This function is available when there is CO
the location of CO
sensor.
2
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
N/A
-
-
44
-
-
-
-
-
-
-
-
-
-
No.45
Supply fan monitor threshold
The threshold fan speed of supply fan monitor output can be
selected.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-62DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
45
-
-
-
-
.
No. 37
Setting
The correction to
check
thermistor detection
0
-7 K (-12.6 °F/-7 °C )
1
-6 K (-10.8 °F/-6 °C )
2
-5 K (-9 °F/-5 °C )
3
-4 K (-7.2 °F/-4 °C )
4
-3 K (-5.4 °F/-3 °C )
5
-2 K (-3.6 °F/-2 °C )
6
-1 K (-1.8 °F/-1 °C )
7
0 K (0 °F/0 °C )
(Factory setting)
8
+1 K (+1.8 °F/+1 °C )
9
+2 K (+3.6 °F/+2 °C )
10
+3 K (+5.4 °F/+3 °C )
11
+4 K (+7.2 °F/+4 °C )
12
+5 K (+9 °F/+5 °C )
13
+6 K (+10.8 °F/+6 °C )
14
+7 K (+12.6 °F/+7 °C )
concentration gap due to
2
Setting
CO
concentration
2
check
correction
0
-500 ppm
1
-400 ppm
2
-300 ppm
3
-200 ppm
4
-100 ppm
5
±0 ppm
(Factory setting)
6
100 ppm
7
200 ppm
8
300 ppm
9
400 ppm
10
500 ppm
Setting
Supply fan monitor
check
threshold
0
Fan speed 1 or higher
(Factory setting)
1
Fan speed 2 or higher
2
Fan speed 3 or higher
3
Fan speed 4
No.46
Exhaust fan monitor threshold
The threshold fan speed of exhaust fan monitor output can be
selected.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
N/A
-
-
-
-
Automatic ventilation mode setting 1)
No.52
Outdoor and indoor temperature gap
Set one of conditions for By-pass mode in auto ventilation operation,
temperature gap between indoor and outdoor.
This function is N/A from Lossnay unit DIP-SW.
This function can also be set on the Auto By-pass settings screen of
the PZ-62DR-E.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
Automatic ventilation mode setting 2)
No.53
The lowest outdoor temperature
Set one of conditions for By-pass mode in auto ventilation operation,
minimum outdoor temperature which comes in indoor directly.
This function is N/A from Lossnay unit DIP-SW.
This function can also be set on the Auto By-pass settings screen of
the PZ-62DR-E.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Eng-21
PZ-62DR-E
Setting
Exhaust fan monitor
check
threshold
Function No. Setting Data
0
Fan speed 1 or higher
(Factory setting)
1
Fan speed 2 or higher
46
2
Fan speed 3 or higher
3
Fan speed 4
PZ-62DR-E
Setting
Gap between Indoor
check
temp. and Outdoor temp.
Function No. Setting Data
0
0 K (0 °F/0 °C ) or more
(Factory setting)
1
1 K (1.8 °F/1 °C ) or more
2
2 K (3.6 °F/2 °C ) or more
3
3 K (5.4 °F/3 °C ) or more
52
4
4 K (7.2 °F/4 °C ) or more
5
5 K (9 °F/5 °C ) or more
6
6 K (10.8 °F/6 °C ) or more
7
7 K (12.6 °F/7 °C ) or more
PZ-62DR-E
Setting
Outdoor temperature
check
Function No. Setting Data
0
50 ˚F (10 ˚C) or more
1
52 ˚F (11 ˚C) or more
2
54 ˚F (12 ˚C) or more
3
55 ˚F (13 ˚C) or more
4
57 ˚F (14 ˚C) or more
5
59 ˚F (15 ˚C) or more
6
61 ˚F (16 ˚C) or more
(Factory setting)
7
63 ˚F (17 ˚C) or more
53
8
64 ˚F (18 ˚C) or more
9
66 ˚F (19 ˚C) or more
10
68 ˚F (20 ˚C) or more
11
70 ˚F (21 ˚C) or more
12
72 ˚F (22 ˚C) or more
13
73 ˚F (23 ˚C) or more
14
75 ˚F (24 ˚C) or more
15
77 ˚F (25 ˚C) or more