Carrier 16LJ-01 Operation Manual page 37

Absorption chiller
Hide thumbs Also See for 16LJ-01:
Table of Contents

Advertisement

3-8-3. Content of alarm and setting point
Table 3-4 List of alarm and setting point in cooling operation
Purpose

Protection of

Chilled water

system


Prevention of

Crystallization


Protection of
generator

Protection of Motor



Others


Display
Chilled water temperature is too low.
Chilled water pump interlock has failure.
Few flow rate of chilled water
Cooling water temperature is too low.
Cooling water pump interlock has failure.
Few flow rate of cooling water
Generator's
temperature is too high.
High concentration of absorbent
Absorbent pump has overload.
Refrigerant pump has overload.
Purge pump has overload.
Ventilation fan interlock etc. have failure.
Capacity is too low.
Cooling tower fan has overload.
Contents of alarm
33
Setting point
2.5℃ or below
-
50% or below
24℃ or below
after 30 minutes
-
50% or below
95℃
65.0% or above
2 times
65.5% or above
Rated current
value or above
-
-
-