3-5-3. Typical indication flow
It shows present data timely in data indication copy (7 segment LED and 6 figures). Indicative
contents shows a data code (contents distinction by a code number) by various operational
time, on/off time,every part temperature, chilled water temterature setting point and alarm
code.
It sends a data code in turn by a ▲▼ key and shows it. It shows an alarm code only when an
abnormality occurrs and, when an abnormality of a plural occurrs, high thing of a privileged
grade is shown and, under numeral right of the alam code dotted "." is shown. Further, an
alame code of a plural is shown in oeder by means of a ▲▼ key when existing.
When it pushes whether threr is no key operation and a "Back" key for 1 minute, it becomes a
generator temperature indication.
Table 3-1 Typical indication flow
Data code
-
Genarator temperature
↑
1.
Chiller operation hours
▲
2.
Absorbent pump operation hours
▼
3.
#2 absorbent pump operation hours
↓
4.
Combustion hours
5.
Refrigerant pump operation hours
6.
Purge pump operation hours
7.
Chiller on/off times
8.
Absorbent pump on/off times
9.
#2 absorbent pump on/off times
A.
Combustion on/off times
B.
Refrigerant pump on/off times
C.
Purge pump on/off times
10.
Chilled water temperature setting point
11.
Hot water temperature setting point
12.
Chilled water inlet temperature
13.
Chilled water outlet temperature
14.
Cooling water inlet temperature
15.
Condenser temperature
16.
Steam drain/exhaust gas temperature
17.
Purge tank pressure
-
Generator temperature
Data name
27
Display
135℃
12355hours
5235hours
No use
No use
503hours
107hours
63times
1071times
No use
No use
87times
3022times
7.0℃
55℃
11.9℃
6.8℃
31.8℃
34.7℃
No use
8.5kPa
135℃
Means