Reducing Bearing Currents During Operation With Converter (Low Voltage) - Siemens SIMOTICS SD SH 71 315 Series Operating Instructions Manual

Low voltage motors
Table of Contents

Advertisement

Preparing for use
4.13 Converter operation
4.13.3

Reducing bearing currents during operation with converter (low voltage)

Taking the following actions will reduce the bearing currents:
• Ensure that the contacts are made over a large area. Solid copper cables are not suitable
for high-frequency grounding because of the skin effect.
Equipotential bonding conductors:
Use equipotential bonding conductors:
• between motor and driven machine
• between motor and converter
• between the terminal box and the RF grounding point at the motor enclosure.
Selecting and connecting the cable:
As far as possible, use symmetrically arranged, shielded connection cables. The cable
shielding, made up of as many strands as possible, must have good electrical conductivity.
Braided shields made of copper or aluminum are very suitable.
• The shield is connected at both ends, at the motor and converter.
• To ensure good discharging of high-frequency currents, provide contacting over a large
surface area:
– as contact established through 360° at the converter
– at the motor, for instance with EMC glands at the cable entries.
• If the cable shield is connected as described, then it ensures the specified equipotential
bonding between the motor enclosure and converter. A separate RF equipotential
bonding conductor is then not necessary.
• If the cable shield is not connected due to special secondary conditions, or not adequately
connected, then the specified equipotential bonding is not provided. In this particular
case, use a separate RF equipotential bonding conductor:
– Between the motor enclosure and protective ground rail of the converter.
– Between motor enclosure and driven machine
– Use braided flat copper straps or high-frequency cables with finely-stranded
– Ensure that the contacts are made over a large area.
40
Concentric copper or aluminum shield
conductors for the separate RF equipotential bonding cable.
Steel armor
1LE7 shaft heights 71 ... 315
Operating Instructions, 04/2022, A5E51689275A-AA

Advertisement

Table of Contents
loading

Table of Contents