Setup Alarms - Victron energy VBC-HV Manual

Ve.net battery controller
Table of Contents

Advertisement

Setup alarms

[Press Enter]
Note: If you can not find the "Setup alarms" menu, make sure that your
VPN is in "user and install" mode.
4.3.2
Alarm options explained
Name
Low
The battery voltage has to be below this threshold to
voltage
trigger the low voltage alarm.
Low
The threshold that has to be reached again to cancel
voltage clr
an active low voltage alarm.
Low volt.
The type of action to take when the alarm condition is
action
met.
High
The battery voltage has to be above this threshold to
voltage
trigger the high voltage alarm.
High
The threshold that has to be reached again to cancel
voltage clr
an active high voltage alarm.
High volt.
The type of action to take when the alarm condition is
action
met.
Low SOC
The low state of charge threshold that will activate the
alarm.
Low SOC
The state of charge threshold that has to be reached to
clr
cancel an active state of charge alarm.
Low SOC
The type of action to take when the alarm condition is
action
met.
Low current
The level below which a low current alarm will be
triggered.
Low current
The level above which a low current alarm will be
clr.
cleared.
Low current
The type of action to take when a low current alarm is
action
active.
High
The level above which a high current alarm will be
current
triggered.
High
The level below which a high current alarm will be
current clr
cleared.
High cur.
The type of action to take when a high current alarm is
action
active.
Enable
The amount of time an alarm condition must be present
delay
in order to trigger the alarm.
Disable
The amount of time an alarm clear condition must be
delay
present in order to disable the alarm.
Min. enable
The minimum amount of time the relay may remain
time
closed once an alarm condition has occurred.
Step 3.) Press "Enter" to enter the "Setup
alarms" menu.
Setup alarms
Description
Default
Rang
Value
e
126 V
96-384
126 V
96-384
None
None,
Relay,
Panel,
Both
192 V
96-384
192 V
96-384
None
None,
Relay,
Panel,
Both
50 %
0-100
80 %
0-100
None
None,
Relay,
Panel,
Both
-100 A
-30000
– 0
-90 A
-30000
– 0
None
None,
Relay,
Panel,
Both
0 –
100
30000
0 –
90
30000
None
None,
Relay,
Panel,
Both
0 – 255
0 s
0 – 255
0 s
0 – 255
0 min
13
Step
size
0.1
0.1
0.1
0.1
1
1
5
5
5
5
1
1
1