Unit Rigging & Assembly; Rigging - BAC PCT Cooling Tower Rigging & Assembly Instructions

Table of Contents

Advertisement

2
PCT COOLING TOWER
Unit Rigging & Assembly
NOTE: For weight information,
refer to the submittal drawing
package.
No. of
NOMINAL
BOX
Basin
SIZES
Sections
5' x 5'
6' x 6'
7' x 7'
8' x 8'
7' x 10.5'
9' x 9'
1
8' x 12'
10' x 10'
11' x 11'
9' x 13.5'
10' x 15'
11' x 16.5'
*** Casing Section Includes Roof Deck (Fan Assembly) ***
NOTE: Any motors or
accessories shipped in the
cold water basin must be
removed prior to installation.
WARNING: Unless units ship
fully assembled, basin &
casing/roof deck sections
must be rigged separately.
Never assemble the unit
before lifting as the lifting
devices provided on the unit
are not designed to support
the weight of the entire
assembled unit.
THE USE OF SAFETY SLINGS IS
RECOMMENDED FOR
EXTENDED LIFTS OR
WHENEVER HAZARDS EXIST.
M A R 1 0 9 - 1
4
W W W . B A L T I M O R E A I R C O I L . C O M . A U

Rigging

To simplify shipping, rigging and installation all PCT Cooling Towers are
shipped in major sections consisting of a basin assembly(s) and one or
more casing/roof deck sections (see Table 1).
NOMINAL
Casing
BOX
Basin
SIZES
Sections
-
-
-
8' x 16'
-
9' x 18'
2
each
-
10' x 20'
11' x 22'
-
-
-
The proper rigging sequence for the PCT series is to lift the basin
section(s) into place first. On multi-section basins lift each section into
place separately and then bolt sections together. Next, lift each casing
section into place and secure to the basin section. If motor(s) are
supplied loose fit the motors. At the completion of this stage a crane is
no longer required.
Finally securely bolt the unit to supporting steel and on multi-section
basins seal the joint between sections.
Table 1 gives the recommended dimensions for rigging each section of
any PCT unit. With the information from the table and the additional
instructions on the following pages the rigging of a PCT Cooling Tower
can be quickly accomplished.
No. of
NOMINAL
Casing
BOX
Basin
SIZES
-
-
-
8' x 24'
-
9' x 27'
each
-
10' x 30'
11' x 33'
-
-
-
No. of
H1
H2
Casing
(fig 2a)
(fig 3)
Sections
(mm)
(mm)
1200
1700
1600
1900
1900
2200
2200
2500
2900
2200
2400
2700
3
each
3500
2500
2700
3000
2900
3300
4000
2700
4500
3000
5000
3300
Table 1. Recommended Dimensions for Rigging
L
(fig 3)
(mm)
1500
1800
2100
2400
3300
2800
3700
3000
3400
4200
4700
5100

Advertisement

Table of Contents
loading