RIGGING

General Notes
1. Never assemble the unit before lifting, as the lifting devices
provided are not designed to support the weight of the entire
assembled unit.
2. Spreader bars of the full width of the section must be used
between the lifting cables to prevent damage to the section.
For extended lifts or where hazards exist, it is recommended to
use the lifting devices in conjunction with safety slings placed
under the unit.
3. Lifting devices have been provided on all sections. The tables
below give the preferred method for rigging each section of a
unit.
Figure 1: Rigging method VL units
1. Spreader Bar; 2. Lifting Device; 3. Safety Slings; 4. Spreader Bar Length.
COOLING TOWERS VTL
Minimum
Model N°
"H
(mm)
VTL-039 to VTL-079
3100
VTL-076 to VTL-095
4300
VTL-089 to VTL-137
5000
VTL-139 to VTL-227
4300
VTL-225 to VTL-272
5000
Table 1: Rigging method VTL and discharge accessory
1
Discharge accessories can be: positive closure damper, tapered
discharge hood, sound attenuation.
CLOSED CIRCUIT COOLING TOWERS VFL
Minimum
Model N°
"H
(mm)
VFL-241 to VFL-243
3100
VFL-361 to VFL-383
3100
Table 2: Rigging method VFL and discharge accessory
4
Spreader
Discharge
Bar
1
Accessory
Length
Minimum "H"
(mm)
1250
3100
1250
4300
1250
5000
2450
4300
2450
5000
Spreader
Discharge
Bar
1
Accessory
Length
2
Minimum "H"
(mm)
1250
3100
1250
3100
CLOSED CIRCUIT COOLING TOWERS VFL
Minimum
Model N°
"H
(mm)
VFL-481 to VFL-484
3700
VFL-721 to VFL-724
3100
VFL-961 to VFL-964
3700
Table 2: Rigging method VFL and discharge accessory
1
Discharge accessories can be: positive closure damper, tapered
discharge hood, sound attenuation.
2
For asymmetrical load distribution (with external piping) shorten the
slings at one end so the casing is approximately horizontal.
EVAPORATIVE CONDENSERS VCL
Minimum
Model N°
(mm)
VCL-042 to VCL-079
3100
VCL-084 to VCL-133
3100
VCL-131 to VCL-159
3700
VCL-167 to VCL-258
3100
VCL-239 to VCL-321
3700
Table 3: Rigging method VCL and discharge accessory
1
Discharge accessories can be: positive closure damper, tapered
discharge hood, sound attenuation.
2
For asymmetrical load distribution (with external piping) shorten the
slings at one end so the casing is approximately horizontal.
Rigging Method Discharge Accessories
Spreader
Discharge
Bar
Accessory
Length
Minimum "H"
(mm)
1250
3700
2450
3100
2450
3700
Discharge
Spreader
Bar
Accessory
"H
Length
Minimum
(mm)
2
"H"
1250
3100
1250
3100
1250
3700
2450
3100
2450
3700
1
2
1