Process Inputs (Mixed Mode) - Omega SS-015-NA User Manual

Long range wireless process and pulse input smart sensor
Table of Contents

Advertisement

The table below shows the binary-weighted values for the 2-bit Digital Input (DIN) function in mixed
mode.

6.3.3.2 Process Inputs (Mixed Mode)

The following process input configuration options are available in mixed input mode: 4-20 mA current
loop, 0-1.0 V voltage input, 0-2.0 V voltage input. Current loop readings are rounded to the nearest 0.1
mA and voltage readings are rounded to the nearest 10 mV. The process input is on pin 4 of the M12 5-
pin connector when in mixed input mode.
6.3.3.2.1 4-20 mA Device Connection
An input channel configured for 0-24 mA can measure the output of a 4-20 mA device. The
Current Loop interface measures the current into the selected input by converting it to a
voltage measurement across a fixed 49.9-ohm resistor. The connection diagram in mixed input
mode is similar to Figure 6 but only the input on pin 4 is valid for 4-20 mA measurements.
Input 1
Input 0
Inactive
Inactive
Inactive
Active
Active
Inactive
Active
Active
Reading
0
1
2
3
17 |
P a g e

Advertisement

Table of Contents
loading

Table of Contents