• Parity: A means of checking the correctness of a character by adding an extra bit to the character and setting
the value based on all the other bits in the character.
• StopBits: The number of bits used to indicate the end of the character.
When the user has completed setting the communication parameters for the device, click Finish.
6.3

Input Configuration

The SS-015 can accept up to three 0-24 mA, 0-1.0 V
one process and one digital input. These modes are detailed in the below sections.

6.3.1 Process Inputs Interface

To configure the process inputs, follow the steps below:
Step 1: Click the Inputs configuration tab on SYNC and choose from Single, Dual, or Triple Process in the Type
dropdown.
Step 2: Click on each input channel and choose between the mA and mV options from the Device Range/Type
drop-down. Click Apply Settings when done.

6.3.1.1 4-20 mA Device Connection

An input channel configured for 0-24 mA can measure the output of a 4-20 mA device. The Current Loop
interface measures the current into the selected input by converting it to a voltage measurement across
a fixed 49.9-ohm resistor.
, or 0-2.0 V
process inputs, one digital pulse input, or a mix of
DC
DC
Figure 6: SYNC interface triple process
Figure 7: 4-20 mA device connection diagram
10 |
P a g e