2. Control Functions
Control functions on the module

Current limit function (Power demand control)
a. Contents of activation
It is possible to operate below a maximum current limitation ratio previously set at the LCD screen. The selection to
enable or release the setting value is performed with the order signal from the local control board.
Also, the overcurrent protection control is always enabled, even in a state where this function is disabled.
b. Setting method
In the case of air-cooled systems
N O T E
Input the ratio corresponding to the "Standard current value" displayed on the LCD screen. Please confirm the setting
value displayed on "Current limitation setting value". This control becomes disabled when selecting "100%".
23
SMGB0082 rev.1 - 07/2015
Display the input window with [INPUT] key
Input the setting value with up and down keys
Confirm with [ENT] key