2. Control Functions
Control of Master/Slave group

2.3.5 Setting items

Water temperature
Addition
Reduction
¦
¡
Outlet water temperature
 Water temperature setting
Sets the temperature in degrees of the outlet water from
the chiller unit to which the water temperature has to be
controlled.
Settings  are  performed  at  the  Master  module  LCD 
screen of unit 1. The setting method is the same as with
the settings of individual operation. By changing the
settings of Master module, the settings of slaves 2~8 are 
also changed automatically.
Please refer to
"2.1 Control functions on the module"
¢ Setting temperature difference
Sets the target difference between water inlet and outlet
temperature to increase the number of units in operation.
£ Temperature range of addition
Sets the range of change of inlet water temperature to
add units, in case that the difference of temperature
reaches the temperature difference set at ¢.
 Temperature range of reduction
Sets the range of change of inlet temperature to reduce
units, in case that the difference of temperature reached
the temperature difference set at ¢.
 Waiting time for effect of addition
Sets the time during which the next addition process is
prohibited, after having added once (start-up of 1 unit).
Recommended > 3 minutes
 Waiting time for effect of reduction
Sets the time during which the next reduction process
is prohibited, after having reduced once (stop of 1 unit).
Recommended > 3 minutes
Settings ¢ to  are performed at the Number of units setting screen. Please refer to
58
SMGB0082 rev.1 - 07/2015
Inlet water temperature
§ Number of Units at Startup
Addition
¥
 Maximum number of operating units
£
¤
© Minimum number of operating units
¢
 Pump operation
Time
 Priority setting
Number of the
Priority setting
eration conditions through the LCD screen".
Sets the number of modules to be started up upon
system start-up.
Sets the upper limit of the number of modules that can
be operated at the same time.
Sets the minimum number of modules to be operated at
light load operation.
Selects batch or individual.
When selecting individual, pump operation order is
linked to the run/stop of the module.
When selecting batch, all the modules which are target
of  the  control  of  group  (Master/Slave)  during  system 
operation set pump operation order to ON continuously.
It is possible to set a priority order, when it is necessary
to operate a certain unit preferentially.
It is possible to set up to 8 steps for priority order.
In case that there are multiple modules with the same
priority order, they operate in rotation.
1
2
3
4
module
1
1
1
2
In case that there is a load
This 3 units are
exceeding the amount of 3
operated with the
units, one unit out of these 4
maximum priority, with
is chosen for startup, with a
a rotation based on
rotation based on operation
operation time
time.
N O T E
The operation time of units with higher priority order
becomes longer.
"2.3.6 Method for setting and confirmation of op-
5
6
8
7
3
2
2
2
This unit is
the last one
to start up