Wireless manual call point (apollo front)

Advertisement

Device activation
1
Device resetting
1
Alarm LED illuminated
Specification
Operating temperature
Storage temperature
Humidity
Supply
CAUTION!
Fitting of an incorrect battery type invalidates the product certification and
may result in poor performance.
IP rating
Operating frequency
Output transmitter
power
Dimensions (W x H x D)
Weight
Location
Protocol
©2021 EMS Ltd. All rights reserved
2
(With transparent cover lifted)
2
(With transparent cover lifted)
-10 to +55 °C
5 to 30 °C
0 to 95% non-condensing
6x AA alkaline (Panasonic LR6AD Powerline
/ Varta 4006 Industrial)
IP24
868 MHz
Auto adjusting 0 to 14 dBm (0 to 25 mW)
90 x 98 x 72.5 mm
0.35 kg
Type A: For indoor use
X2
Turn the reset
key clockwise
to reset
Regulatory information
Manufacturer
Year of manufacture
Certification
Certification
body
CPR DoP
Approved to
European Union
directives
Page 2 of 2
3
illuminated and fire
event is displayed at
3
Carrier Manufacturing Polska Sp. Z o.o. Ul. Kolejowa
24. 39-100 Ropczyce, Poland
See devices serial number label
19
0905
0359-CPR-00694
EN54-11:2001. Incorporating Amendment No. 1 and
Corrigendum No. 1. Fire detection and fire alarm
systems. Part 11: Manual call points.
EN54-25:2008. Incorporating corrigenda September
2010 and March 2012. Fire detection and fire alarm
systems. Part 25: Components using radio links.
EMS declares that this device is in compliance with
Directive 2014/53/EU. The full text of the EU
declaration of conformity is available at the following
internet address: www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
Dispose of your batteries in an environmentally
friendly manner according to your local regulations.
MK289-99 Iss 3 23/11/2021
Alarm LED
the control panel.
Element
returns to
the normal
position
AJM