Type &
Object name
Instance
Relay 4 Control
BV10
Relay 5 Control
BV11
Relay 6 Control
BV12
Relay 7 Control
BV13
Occupancy
BV 14
Command
Fan Output for
BV15
Heating
Sensor type
BV16
Fan Mode
MSV 1
System Mode
Sleep
Temperature Source
Lowest Fan Speed
Fan Speed Status
MSV 5
Object name
Type &
Instance
Baud Rate
MSV 6
UM-15090000-AA8
Readable/
Writable
R/W
R/W
R/W
R/W
R/W
R/W
R/W
MSV 0
R/W
R/W
MSV 2
R/W
MSV3
R/W
MSV 4
R/W
R
Readable/
Writable
R/W
Description
On/Off Control of Relay 4
(Heating Stage 2)
On/Off Control of Relay 5
On/Off Control of Relay 6
On/Off Control of Relay 7
Fan
Room Occupancy Setting
Disable/ Enable Fan
Output for Heating
Select Sensor type
Fan Mode
Working Mode: Heat, Cool or
Ventilation
Sleep (Only for Models with
Sleep Function Available).
Current Temperature Source
Lowest Fan speed in
Auto Fan mode
Fan Speed Status
Description
Baud rate
(BACnet MS/TP)
Range and Definition
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Occupied,
1: Unoccupied
0: Disable
1: Enable
0: CO2
1: RH
1: Auto 2: Low
3: Med.4: Hi
1: Cool Mode
2: Heat Mode
3: Ventilation @ Cool Mode
4: Ventilation @ Heat
Mode
1: Disable,
2: 0 Hr. Sleep
3: 0.5 Hr. Sleep
4: 1 Hr. Sleep
5: 1.5 Hrs. Sleep,
6: 2 Hrs. Sleep
1: Built-In Temp. Sensor 2:
Remote Temp. Sensor 3:
Assigned through BACnet
1: Stop 2: Low
3: Med. 4: Hi.
1: Stop 2: Low
3: Med 4: Hi
Range and Definition
1: 9600 bps
2: 19200 bps
3: 38400 bps
4: 57600 bps
5: 76800 bps
Page 33