Type &
Object name
Instance
Med. Fan Speed
Setting
AV 44
Hi Fan Speed
AV 45
Setting
Minimum Off
AV 46
Time
Minimum On Time
AV 47
Stroke Time
AV 48
Set Point for
Humidity
AV 49
Dew Point Set
AV 50
Point
Occupancy Status
BI 0
Window-Door Status
BI 1
BI 2
Cooling-heating
Status
Relay 1 Status
BI 3
Relay 2 Status
BI 4
Relay 3 Status
BI 5
Relay 4 Status
BI 6
Relay 5 Status
BI 7
Relay 6 Status
BI 8
Relay 7 Status
BI 9
Dl 1 Status
BI10
Dl 2 Status
BI11
Object name
Type &
Instance
Dl 3 Status
BI12
Dl 4 Status
BI13
Dl 5 Status
BI14
Dl 6 Status
BI15
UM-15090000-AA8
Readable/
Description
Writable
Med. Fan Speed Setting (for
Modulating Fan
Application)
R/W
Hi Fan Speed Setting(For
R/W
Modulating Fan Application)
R/W
Minimum Off Time
R/W
Minimum On Time
Stroke time
R/W
Set Point for Humidity
Control
R/W
Dew Point Temperature
R/W
Set Point
R
Status of Occupancy
R
Window/ Door Status
Status of Cooling/Heating
R
Control
Output
Status of Relay 1
R
(Cooling Stage 1)
Status of Relay 2
R
(Cooling Stage 2)
Status of Relay 3
R
(Heating Stage 1)
Status of Relay 4
R
(Heating Stage 2)
Status of Relay 5
R
Status of Relay 6
R
Status of Relay 7
R
Fan
Status of Digital Input 1
R
Status of Digital Input 2
R
Description
Readable/
Writable
Status of Digital Input 3
R
Status of Digital Input 4
R
Status of Digital Input 5
R
Status of Digital Input 6
R
Range and Definition
Reg 52~Reg54
Reg 53~100%
0~180 seconds
0~180 seconds
10~1600 sec.
0~1000 (0.0~100.0
%RH)
℃/°F
-999~9999: -99.9~999.9
0: Room Occupied
1: Room Unoccupied
0: Door/Window Closed
1: Door/Window Open
0: Close & Off 1: Open & On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
Range and Definition
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
0: Off, 1: On
Page 31