Page 1
Improperly installed, adjusted or altered equipment by an unqualified pers on could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. TTV-IOM-R410A DECEMBER 2021 690883990001 Confidential and proprietary Trane information...
Contents Model Nomenclature System Precaution General Information General Data Installation Operation / Start-Up Maintenance Dimensional Data Electrical Wiring TTV-IOM-R410A...
If the capacity of the power circuit is insufficient or there is • The place that contain sulfuric acid, such as hot springs. insufficient electrical work, it could result in a fire or an • The place where high frequency devices or wireless devices electric shock. are used. TTV-IOM-R410A...
This manual covers the installation, operation and maintenance Warranty of the Trane TTV DX Fan Coil. These new air handler models Warranty is based on the general terms and conditions of the are completely designed to incorporate a single slab coil Trane Company.
Connections to outdoor units clearance must be provided. can be made from the left or right hand side of the TTV. 4. All duct work should be properly insulated to prevent Caution: Protect adjacent surfaces from heat damage, when condensation and heat loss.
Check and retighten, if necessary, drive and bearing bolts, motor clamp plate bolts and isolator bolts. Check to ensure that pulley are correctly aligned and that shafts are parallel. Check belt tension as per instruction given in the maintenance section. TTV-IOM-R410A...
Operation Section. 4. Inspect the condition of the evaporator fan belt and replace Force if necessary. The belts fitted to TTV units cannot achieve design performance without the correct tensioning. 5. Check condition of vibration isolators, replace if there is any Deflection sign of wear, loosening or material deterioration.
Page 11
A zero voltage reading indicates no voltage drop. If any reading is obtained, a voltage drop exists and should be 100 x (393-380) + (398-393) + (400-393) corrected. Inspect the contacts and replace if necessary. 2x393 = 3.2% TTV-IOM-R410A...
Dimensional Data TTV 250 FAN ARRANGEMENT 1 1808 RECOMMENDED 1774 RECOMMENDED CLEARANCE 588.5 588.5 CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 16" X 20" 16" X 20" 16" X 20" 16" X 20"...
Page 13
Dimensional Data TTV 250 FAN ARRANGEMENT 3 1808 RECOMMENDED 1774 RECOMMENDED CLEARANCE 633.5 633.5 CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 16" X 20" 16" X 20" 16" X 20" 16" X 20"...
Page 14
Dimensional Data TTV 300 FAN ARRANGEMENT 1 1808 RECOMMENDED 1774 RECOMMENDED CLEARANCE 583.5 583.5 CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 15" X 20" 15" X 20" 15" X 25" 15" X 20"...
Page 15
Dimensional Data TTV 300 FAN ARRANGEMENT 3 1808 RECOMMENDED 1774 RECOMMENDED CLEARANCE 633.5 633.5 CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 15" X 20" 15" X 20" 15" X 25" 15" X 20"...
Page 16
Dimensional Data TTV 400 FAN ARRANGEMENT 1 2088 RECOMMENDED 2054 RECOMMENDED CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL ISOMETRIC VIEW COIL REAR TOP VIEW 16" X 25" 16" X 25" 16" X 25" 16" X 25"...
Page 17
Dimensional Data TTV 400 FAN ARRANGEMENT 3 2088 RECOMMENDED RECOMMENDED 2054 CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 16" X 25" 16" X 25" 16" X 25" 16" X 25" 16" X 25"...
Page 18
Dimensional Data TTV 500 FAN ARRANGEMENT 1 2596 RECOMMENDED 2562 RECOMMENDED CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL ISOMETRIC VIEW COIL REAR TOP VIEW 16" X 25" 16" X 20" 16" X 25" 16" X 25"...
Page 19
Dimensional Data TTV 500 FAN ARRANGEMENT 3 2596 RECOMMENDED RECOMMENDED 2562 CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL ISOMETRIC VIEW COIL REAR TOP VIEW 16" X 25" 16" X 20" 16" X 25" 16" X 25"...
Page 20
Dimensional Data TTV 600 FAN ARRANGEMENT 1 2596 RECOMMENDED RECOMMENDED 2562 CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 20" X 20" 20" X 25" 20" X 25" 20" X 25" 20" X 20"...
Page 21
Dimensional Data TTV 600 FAN ARRANGEMENT 3 2596 RECOMMENDED RECOMMENDED 2562 CLEARANCE CLEARANCE FRONT 38 DIA. KNOCKOUT FOR POWER SUPPLY AND CONTROL COIL REAR TOP VIEW 20" X 25" 20" X 20" 20" X 25" 20" X 25" 20" X 25"...
Page 22
Dimensional Data TTV 800 FAN ARRANGEMENT 1 TTV-IOM-R410A...
10 hp (7.5 kW) 15 hp (11 kW) 20 hp (15 kW) W1 , U2 , V2 & W2. TTV600 15 hp (11 kW) 20 hp (15 kW) ----- ----- TTV800 20 hp (15 kW) 25 hp (18.5 kW) ----- ----- TTV-IOM-R410A...
Page 24
For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
Need help?
Do you have a question about the TTV and is the answer not in the manual?