Trane ODYSSEY TTA Series Installation Operation & Maintenance
Trane ODYSSEY TTA Series Installation Operation & Maintenance

Trane ODYSSEY TTA Series Installation Operation & Maintenance

Light commercial split system 4-20 tons tta model 50 hz
Hide thumbs Also See for ODYSSEY TTA Series:

Advertisement

Quick Links

Installation Operation
Maintenance
ODYSSEY
Light Commercial
Split System 4-20 Tons
TTA Model 50 Hz
Single Circuit
TTA 051 JDF
TTA 065 JDF
TTA 075 JDF
TTA 100 JDF
TTA 120 JDF
TTA 150 JDF
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified pers on could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
May 2020
Dual Circuit
TTA 150 JD00
TTA 180 JD00
TTA 200 JD00
TTA 240 JD00
SAFETY WARNING
TTA-R410A
690883650001
Confidential and proprietary Trane information
Manifolded Compr.
TTA 150 JD0G
TTA 180 JD0G
TTA 200 JD0G
TTA 240 JD0G
R410A

Advertisement

Table of Contents
loading

Summary of Contents for Trane ODYSSEY TTA Series

  • Page 1 Improperly installed, adjusted or altered equipment by an unqualified pers on could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. TTA-R410A May 2020 690883650001 Confidential and proprietary Trane information...
  • Page 2: Model Nomenclature

    Model Nomenclature Air-Cooled Condensing Unit Model Nomenclature T T A 1 5 0 J D F 0 F C Product Type Service Digit TTA = Cooling Only Condensing Unit = Minor Design = Minor Design with Flex Tube Nominal Gross Cooling Capacity (MBH) 051 = 51 MBH Minor Design Sequence 065 = 65 MBH...
  • Page 3: Table Of Contents

    Contents Model Nomenclature System Precaution General Information Installation Refrigerant Piping Guidelines Refrigerant Charging and Evacuation General Data Refrigerant Circuit Electrical Wiring Dimensional Data Operation Maintenance Trouble Shooting TTA-R410A...
  • Page 4: System Precaution

    System Precautions Safety Precautions WARNING • Attach the electrical cover to the indoor unit and the To prevent injury to the user or other people and property service panel to the outdoor unit securely. damage, the following instructions must be followed. •...
  • Page 5: General Information

    General Information Installation Checklist Inspection Checklist This manual covers the installation of the TTAB51, TTAB65, TTA075, TTA100 An “Installation Checklist” is provided To protect against loss due to ,TTA120 and TTA150 (Single Circuit) at the end of the installation section damage incurred in transit, complete TTA150, TTA180, TTA200 and TTA240 of this manual.
  • Page 6: Installation

    Installation Lifting Recommendations Clearances Before preparing the unit for lifting, Provide enough space around the estimate the approximate center of unit to allow unrestricted access gravity for lifting safety. Because of to all service points. Refer to unit placement of internal components, dimensional data for minimum the unit weight may be unevenly required service and free air...
  • Page 7: Refrigerant Piping Guidelines

    Notes: 1. Two line sets are required for dual circuits units. minimum number of bends and 2. For line lengths over 80 linear feet and 15 feet liquid line riser, reducers) and minimum consult your local Trane representative. amount of line exposed to outdoor ambients. TTA-R410A...
  • Page 8 Refrigerant Piping Guidelines Refrigerant Piping Procedures 1. Remove both seal caps from the All brazing should be done using 2 indoor unit connection stubs. (Outdoor units) through the pipe being brazed 9 Each TTA unit ships with dry nitrogen Caution: Do not remove seal caps (Figure 2).
  • Page 9: Refrigerant Charging And Evacuation

    Refrigerant Charging and Evacuation System Evacuation 1. After completion of leak check, evacuate the system. 2. Attach appropriate hoses from TTA B51 JDF 3.90 8.60 manifold gauge to gas and liquid TTA B65 JDF 3.30 7.27 line pressure taps. TTA 075 JDF 5.40 11.90 TTA 100 JDF...
  • Page 10 Refrigerant Charging and Evacuation Caution Liquid Charging (Figure 3) Pressure reading should fall Freon Gas only. approximately at the points shown After the refrigerant pipework system Always evacuate air from the tubing by the pressure curves in Service has been pressure tested and before adding refrigerant.
  • Page 11: General Data

    General Data TTA-R410A...
  • Page 12 General Data UNIT MODELS TTA150JD00 TTA180JD00 TTA200JD00 TTA240JD00 POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 43.28 45.53 43.28 51.15 SYSTEM DATA Refrigerant Type R410A R410A R410A R410A Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant Charge lb (kg) Holding Charge Dual Circuit.
  • Page 13 General Data UNIT MODELS TTA150JD0G TTA180JD0G TTA200JD0G TTA240JD0G POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 30.90 36.08 42.38 47.55 SYSTEM DATA Refrigerant Type R410A R410A R410A R410A Refrigerant Connection Type BRAZE BRAZE BRAZE BRAZE Refrigerant Charge lb (kg) Holding Charge Single Circuit.
  • Page 14: Refrigerant Circuit

    Refrigerant Circuit Figure 4A TTA B51-B65 JDF (Single Circuit) TTA 075-150 JDF (Single Circuit) TTA 150-240 JD00 (Dual Circuit) Figure 4B TTA 150-240 JD0G (Manifolded Comp.) TTA-R410A...
  • Page 15: Electrical Wiring

    Electrical Wiring Electrical Wiring Warning: Important: Unit Power Supply Caution: Table 5 - Electrical Data 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 342-440 TTA-R410A...
  • Page 16 Electrical Wiring WIRING DIAGRAM TTA B51-B65 JDF (SINGLE CIRCUIT) ELEMENTARY DIAGRAM 1M-1 1M-2 COMPR. MOTOR 1M-3 NEUTRAL GROUND TERMINAL MOTOR 9 18 1R-11,12 1M-1,2,3 CONNECTION DIAGRAM T1 T2 3 1R 4 4 6 5 L N C L1 L2 L3 N COMPRESSOR INTERNAL OVERLOAD TO INDOOR UNIT...
  • Page 17 Electrical Wiring WIRING DIAGRAM TTA 075-150 JDF (SINGLE CIRCUIT) ELEMENTARY DIAGRAM 1M-1 1M-2 COMPR. MOTOR 1M-3 NEUTRAL GROUND TERMINAL MOTOR 1R-11 2M-A1 1M-1,2,3 EXTERNAL CONTROL 2M-11,14 2M-A2 CONNECTION DIAGRAM 3 1R 4 T1 T2 4 6 5 COMPRESSOR INTERNAL OVERLOAD POWER SUPPLY 380V./3PH./50HZ.
  • Page 18 Electrical Wiring TTA 150-240 JD00 (DUAL CIRCUIT) WIRING DIAGRAM ELEMENTARY DIAGRAM 1M-1 1M-2 COMPR. MOTOR NO.1 1M-3 NEUTRAL MOTOR NO.1 GROUND TERMINAL 2M-1 14 28 2M-2 COMPR. MOTOR NO.2 2M-3 MOTOR NO.2 1HTR 2HTR 7 1R 1R-16 3M-A1 1TH-1 1M-1,2,3 2R-18 1TH-2 2M-8,9,10...
  • Page 19 Electrical Wiring TTA 150-240 JD0G (Manifolded Compressor) WIRING DIAGRAM ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM 1M-1 1M-2 COMPR. T2 MOTOR NO.1 1M-3 NEUTRAL 2M-1 2M-2 COMPR. T2 MOTOR GROUND NO.2 TERMINAL 2M-3 3M-1 N 14A 3M-2 MOTOR 3M-3 NO.1 MOTOR 1HTR NO.2 2HTR 1R-16 7 1R...
  • Page 20: Dimensional Data

    Dimensional Data TTA B51/B65 JDF (SINGLE CIRCUIT) Vertical Discharge 29.5 29.5 TTAB51 A = ELECTRIC WIRING OUTLET B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”) C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”) TTAB65 A = ELECTRIC WIRING OUTLET B = GAS LINE CONNECTION FEMALE BLAZED (DIA 7/8”) C = LIQUID LINE CONNECTION FEMELE BLAZED (DIA 1/2”) 106.8...
  • Page 21 Dimensional Data TTA 075/100/120 JDF (SINGLE CIRCUIT) HORIZONTAL AND VERTICAL DISCHARGE TTA-R410A...
  • Page 22 Dimensional Data TTA 150 JDF (SINGLE CIRCUIT) HORIZONTAL AND VERTICAL DISCHARGE TTA-R410A...
  • Page 23 Dimensional Data TTA 150/180/200/240 JD00 (DUAL CIRCUIT) TTA-R410A...
  • Page 24 Dimensional Data TTA 150/180/200/240 JD0G (MANIFOLDED COMPRESSOR) TTA-R410A...
  • Page 25: Operation

    Operation Sequence of Operation Safety Controls • Inspect unit location for proper Note: All of these controls may not be required service clearances. General installed on your unit, check electrical • Inspect unit location for proper free Operation of the system cooling schematic.
  • Page 26: Maintenance

    Maintenance Maintenance • Inspect the evaporator and • Remove any accumulation of dust condenser coils for dirt and debris. and/or dirt from the unit casing. Perform all of the indicated If the coils appear dirty, clean them. • Remove corrosion from any surface maintenance procedures at the •...
  • Page 27: Trouble Shooting

    Trouble Shooting Table 6: Troubleshooting Chart P : primary cause S : secondary cause Refrigerant Circuit Liquid overfeeding (expansion valve) (cap tube) f l i or no cooling/heating Electrical Compressor and outside fan won’t start Compressor will not start but outside fan runs Outside fan won’t start Compressor hums but won’t start...
  • Page 28 For more information, please visit trane.com or tranetechnologies.com. Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

Table of Contents