Automatic restart.
Can cause death or serious injury.
If a starting command is pending, a restart will be triggered automatically after the reset. This
particularly applies if the motor protection has tripped. Dangerous states of the system can
result.
Reset the start command (e.g. via the PLC or switch) before performing a reset.
To do this, for example, link the group error output (terminals 95 and 96) into the control.
Wiring of control circuit for control by switch
F1
S1
S4
Q1
Q11
P1
M1
PE
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
WARNING
Fuse
Switch: Motor On / Off
Pushbutton: Reset
Motor starter protector
3RW55 soft starter
Indicator light
Motor
Protective conductor
Example circuits
A.2 Control circuit connection