Simulation - Siemens SIRIUS 3RW55 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW55:
Table of Contents

Advertisement

Functions
8.19 Test mode
Setting options
Automatic starting in test operation (test with a small load)
Can cause death or serious injury.
The 3RW55 and 3RW55 Failsafe soft starters immediately continue to operate with the values
set by the control once test operation has been activated. Outputs are activated when the ON
condition is met.
Take appropriate measures to prevent unintentional starting and to ensure a defined start of
the system.
• 3RW5 HMI High Feature (from firmware version V2.0)
Menu: "Control > Test mode"
Access protection to 3RW5 HMI High Feature is not active or has been reset.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Commissioning" > Window "Work area" > "Soft Starter > Functions > Test mode"
• With a fieldbus via a 3RW5 communication module (only via a 3RW5 PROFINET or PROFIBUS
communication module):
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
Parameters
Parameters
Activate test with small load
Deactivate test with small load
8.19.2

Simulation

Operating principle
The test mode function "Simulation" is useful for commissioning and troubleshooting because
any situations can be tested without great effort, e.g. wiring modifications, connection of
external devices or interventions in the PLC.
With the test mode function "Simulation", the 3RW55 soft starter virtually simulates the motor
operating states (starting, running, stopping) without main current. The 3RW55 soft starter
224
WARNING
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Description
The 3RW55 or 3RW55 Failsafe soft starter switches to the test mode function "Test with
small load".
The test mode function "Test with small load" is terminated. The 3RW55 or 3RW55
Failsafe soft starter exits the test mode and switches back to the parametrized operating
mode.
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rw55 failsafe

Table of Contents