the auto arming sequence and transmit such cancelation to the signal receiving center with the
identification of the authorized user that canceled the action.
The following options must be enabled in the Protege system when using the Auto Arming feature. When
the defer warning time is programmed to 10 minutes, the output group will be activated 10 minutes before
the system performs the Auto Arming in the associated Area.
-
The Defer Output or Output Group must be programmed. Refer to the section
Operator Reference Manual for programming instructions.
-
The Defer Warning Time must be programmed to not less than 10 minutes. Refer to the section
Configuration
in the Operator Reference Manual.
-
The Defer Automatic Arming option must be enabled. Refer to the section
Operator Reference Manual.
Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Double EOL Input Configuration
Only double EOL Input Configuration shall be used. Refer to the
section
Inputs | Options
Multiplex System and Poll Time
The Protege controller is compatible with the ArmorIP Internet Monitoring Receiver. Poll Time must be set
to 40 seconds and the Grace Time must be set to 20 seconds.
In the Protege system, the reporting service must be configured to 40 seconds. The following options are
required for the service selected as Report IP type:
-
The Log Polling Message option must be enabled. Refer to the section
Operator Reference Manual.
-
The Poll Time must be programmed to 40 seconds. Refer to the
Operator Reference Manual.
Central Station Signal Receiver
The common equipment of each signal receiving center control unit shall be limited to 1000 alarm systems.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a minimum
of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the sequence is
reached, an indication of the failure shall be made at the premises.
In the Protege system, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The Dial Attempts option must be programmed. Refer to the section
ID | Settings
in the Operator Reference Manual.
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Input Service Test Report
-
The Test Report Time must be programmed. Refer to the section
Operator Reference Manual.
-
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Options
in the Operator Reference Manual.
-
The Test Report Time is Periodic option must be enabled. Refer to the section
the Operator Reference Manual.
Primary Communication Channel
The first attempt to send a status change signal shall utilize the primary communication channel.
The Report IP and Contact ID services must be programmed and enabled within the Protege system, and
the CID service must be set as the backup service. The following options are required:
-
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
-
Refer to the section
PRT-PSU-DIN-4A | Protege DIN Rail 4A Intelligent Power Supply | Installation Manual
in the Operator Reference Manual.
Contact ID
in the Operator Reference Manual.
Areas | Outputs
Areas | Options (2)
Inputs
section of this manual and the
Report IP | Options
Report IP | General
Controllers | Configuration
Controller | Options
in the
Areas |
in the
in the
section in the
Contact
in the
Controller |
in
37