Table 1H — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ300) (cont)
NOMINAL
IFM
UNIT
V-PH-Hz
TYPE
STD
STD
208/230-3-60
HIGH STATIC
HIGH STATIC
50HJ012
STD
STD
460-3-60
HIGH STATIC
HIGH STATIC
STD
STD
50HJ014
208/230-3-60
STD
STD
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
— National Electrical Code
NEC
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
HEATER
CONV
62AQ
CRHEATER
OUTLET
FLA
---A00
NONE
017
21.7/ 25.0
010
33.4/ 38.5
NO
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/3 8.5
NO
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
016
013
NO
15.8
014
014+016
013+015
NONE
016
013
YES
15.8
014
014+016
013+015
NONE
016
013
NO
15.8
014
014+016
013+015
NONE
016
013
YES
15.8
014
014+016
013+015
NONE
017
21.7/ 25.0
010
33.4/ 38.5
NO
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
29.8
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
016
013
NO
15.8
016
014+016
013+015
NONE
016
013
15.8
YES
016
014+016
013+015
HEAT
POWER SUPPLY
FUSE OR
FLA
MCA
HACR BKR
—/—
82.8/ 82.8
—
82.8/ 82.8
—
86.4/ 92.8
—
128.1/140.9
—
155.2/172.2
—
175.0/165.0
—
—/—
88.8/ 88.8
—
88.8/ 88.8
—
91.2/ 97.0
—
132.9/145.1
—
160.0/176.4
—
179.8/169.2
—
—/—
87.2/ 87.2
—
87.2/ 87.2
—
90.8/ 97.2
—
132.5/145.3
—
159.6/176.6
—
179.4/169.4
—
—/—
93.2/ 93.2
—
93.2/ 93.2
—
95.6/101.4
—
137.3/149.5
—
164.4/180.8
—
184.2/173.6
—
—
40.7
45.0
16.7
45.8
60.0
19.8
49.7
60.0
33.4
66.7
—
50.2
87.6
—
60.1
85.0
—
—
43.4
45.0
16.7
47.9
60.0
19.8
51.8
60.0
33.4
68.8
—
50.2
89.7
—
60.1
87.1
—
—
43.3
50.0
16.7
48.4
60.0
19.8
52.3
60.0
33.4
69.3
—
50.2
90.2
—
60.1
87.6
—
—
46.0
50.0
16.7
50.5
60.0
19.8
54.4
60.0
33.4
71.4
—
50.2
92.3
—
60.1
89.7
—
—/—
90.4/ 90.4
—
90.4/ 90.4
—
90.8/ 97.2
—
132.5/145.3
—
159.6/176.6
—
179.4/169.4
—
—/—
96.4/ 96.4
—
96.4/ 96.4
—
95.6/101.4
—
137.3/149.5
—
164.4/180.8
—
184.2/173.6
—
—
44.9
50.0
16.7
48.4
60.0
19.8
52.3
60.0
16.7
48.4
—
50.2
90.2
—
60.1
87.6
—
—
47.6
50.0
16.7
50.5
60.0
19.8
54.4
60.0
16.7
50.5
—
50.2
92.3
—
60.1
89.7
—
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
26
SINGLE
DISCONNECT SIZE*
POINT BOX
CRSINGLE
MOCP
FLA
---A00
90/ 90
†
90/ 90
90/ 90
†
90/ 90
100/110
†
90/ 91
150/150
†
123/135
175/175
†
148/164
175/200
†
166/185
100/100
†
96/ 96
100/100
†
96/ 96
110/110
†
96/ 96
150/150
†
129/140
175/200
†
154/169
200/200
†
172/190
100/100
†
95/ 95
100/100
†
95/ 95
100/110
†
95/ 96
150/150
†
128/140
175/200
†
153/169
200/200
†
171/190
100/100
†
101/101
100/100
†
101/101
110/110
†
101/101
150/150
†
134/145
175/200
†
159/174
200/200
†
177/195
—
—
44.0
—
011
44.0
—
011
47.0
80.0
014
62.0
100.0
016
81.0
110.0
016
93.0
—
—
47.0
—
014
47.0
—
011
49.0
80.0
014
65.0
100.0
016
84.0
110.0
016
95.0
—
—
47.0
—
014
47.0
—
011
50.0
80.0
014
65.0
100.0
016
84.0
110.0
016
96.0
—
0.0
50.0
—
014
50.0
—
011
52.0
90.0
014
68.0
100.0
016
87.0
110.0
016
98.0
100/100
†
98/ 98
100/100
†
98/ 98
100/110
†
98/ 98
150/150
†
128/140
175/200
†
153/169
200/200
†
171/190
100/100
†
104/104
100/100
†
104/104
110/110
†
104/104
150/150
†
134/145
175/200
†
159/174
200/200
†
177/195
—
—
49.0
—
014
49.0
—
011
50.0
70.0
014
49.0
100.0
016
84.0
110.0
016
96.0
—
—
51.0
—
014
51.0
—
011
52.0
70.0
014
51.0
100.0
016
87.0
110.0
016
98.0
452 + 464 + 455
3
1371
=
3
= 457
7
LRA
519/519
519/519
519/519
519/519
519/519
519/519
523/523
523/523
523/523
523/523
523/523
523/523
542/542
542/542
542/542
542/542
542/542
542/542
547/547
547/547
547/547
547/547
547/547
547/547
260.0
261.0
261.0
261.0
261.0
261.0
262.0
263.0
263.0
263.0
263.0
263.0
272.0
272.0
272.0
272.0
272.0
272.0
274.0
274.0
274.0
274.0
274.0
274.0
604/604
604/604
604/604
604/604
604/604
604/604
609/609
609/609
609/609
609/609
609/609
609/609
287.0
287.0
287.0
287.0
287.0
287.0
289.0
289.0
289.0
289.0
289.0
289.0