Disconnect - Carrier COBRA 48/50HJ004-014 Installation And Service

Energy recovery units
Table of Contents

Advertisement

Table 1E — Electrical Data (COBRA™ Energy Recovery 48HJ008-014 Units with 62AQ200)
NOMINAL
UNIT
V-PH-HZ
208/230-3-60
48HJ008
460-3-60
208/230-3-60
48HJ009
460-3-60
208/230-3-60
48HJ012
460-3-60
208/230-3-60
48HJ014
460-3-60
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. UL, Canada units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent of voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
IFM
CONV
TYPE
OUTLET
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
HIGH STATIC
NO
HIGH STATIC
YES
STD
NO
STD
YES
STD
NO
STD
YES
21
POWER SUPPLY
62AQ
FUSE OR
FLA
MCA
HACR BKR
21.9
60.1
70
21.9
66.1
70
21.9
63.2
70
21.9
69.2
80
10.2
29.4
35
10.2
32.1
35
10.2
30.8
35
10.2
33.5
35
21.9
62.1
70
21.9
68.1
70
21.9
65.2
70
21.9
65.2
70
10.2
31.7
35
10.2
34.4
40
10.2
33.1
35
10.2
35.8
40
21.9
74.9
80
21.9
80.9
90
21.9
79.3
90
21.9
85.3
90
10.2
35.1
40
10.2
37.8
40
10.2
37.7
40
10.2
40.4
45
21.9
82.5
90
21.9
88.5
100
10.2
39.3
45
10.2
42.0
45
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
DISCONNECT SIZE*
FLA
LRA
66
366
71
371
69
391
75
395
32
184
34
186
34
197
36
199
68
400
73
405
71
425
71
425
34
206
37
208
36
219
38
221
81
465
87
469
86
488
92
493
38
234
40
236
41
245
43
247
89
550
95
555
43
270
45
272
452 + 464 + 455
3
1371
=
3
= 457
7
457