Table 1F — Electrical Data (COBRA™ Energy Recovery 50HJ008-014 Units with 62AQ200) (cont)
NOMINAL
IFM
UNIT
V-PH-Hz
TYPE
STD
STD
208/230-3-60
HIGH STATIC
HIGH STATIC
50HJ012
STD
STD
460-3-60
HIGH STATIC
HIGH STATIC
STD
208/230-3-60
STD
50HJ014
STD
460-3-60
STD
LEGEND
FLA
— Full Load Amps
HACR
— Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
— National Electrical Code
NEC
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
HEATER
CONV
62AQ
CRHEATER
OUTLET
FLA
---A00
NONE
017
21.7/ 25.0
010
33.4/ 38.5
NO
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
NO
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
016
013
NO
10.2
015
014+016
013+015
NONE
016
013
YES
10.2
015
014+016
013+015
NONE
016
013
NO
10.2
015
014+016
013+015
NONE
016
013
YES
10.2
015
014+016
013+015
NONE
017
21.7/ 25.0
010
33.4/ 38.5
NO
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
017
21.7/ 25.0
010
33.4/ 38.5
YES
21.9
012
66.7/ 77.0
012+017
88.4/102.0
010+012
104.2/120.3
NONE
016
013
NO
10.2
015
014+016
013+015
NONE
016
013
YES
10.2
015
014+016
013+015
HEAT
POWER SUPPLY
FUSE OR
FLA
MCA
HACR BKR
—/—
74.9/ 74.9
—
74.9/ 74.9
—
77.6/ 84.0
—
119.3/132.1
—
146.4/163.4
—
166.2/156.2
—
—/—
80.9/ 80.9
—
80.9/ 80.9
—
82.4/ 88.2
—
124.1/136.3
—
151.2/167.6
—
171.0/160.4
—
—/—
79.3/ 79.3
—
79.3/ 79.3
—
82.3/ 88.8
—
124.0/136.9
—
151.1/168.2
—
170.9/160.9
—
—/—
85.3/ 85.3
—
85.3/ 85.3
—
87.1/ 93.0
—
128.8/141.1
—
155.9/172.4
—
175.7/165.1
—
—
35.1
40.0
16.7
37.5
40.0
19.8
41.4
45.0
39.7
66.2
—
50.2
79.3
—
60.1
76.7
—
—
37.8
40.0
16.7
39.6
45.0
19.8
43.5
45.0
39.7
68.3
—
50.2
81.4
—
60.1
78.8
—
—
37.7
40.0
16.7
40.3
45.0
19.8
44.3
50.0
39.7
69.1
—
50.2
82.1
—
60.1
79.6
—
—
40.4
45.0
16.7
42.4
50.0
19.8
46.4
50.0
39.7
71.2
—
50.2
84.2
—
60.1
81.7
—
—/—
82.5/ 82.5
—
82.5/ 82.5
—
82.3/ 88.8
—
124.0/136.9
—
151.1/168.2
—
170.9/160.9
—
—/—
88.5/ 88.5
—
88.5/ 88.5
—
87.1/ 93.0
—
128.8/141.1
—
155.9/172.4
—
175.7/165.1
—
—
39.3
45.0
16.7
40.3
45.0
19.8
44.3
50.0
39.7
69.1
—
50.2
82.1
—
60.1
79.6
—
—
42.0
45.0
16.7
42.4
50.0
19.8
46.4
50.0
39.7
71.2
—
50.2
84.2
—
60.1
81.7
—
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
23
SINGLE
DISCONNECT SIZE*
POINT BOX
CRSINGLE
MOCP
FLA
---A00
80/ 80
†
81/ 81
80/ 80
†
81/ 81
90/ 90
†
81/ 82
125/150
†
114/126
150/175
†
139/155
175/175
†
157/176
90/ 90
†
87/ 87
90/ 90
†
87/ 87
90/100
†
87/ 87
125/150
†
120/131
175/175
†
145/160
175/175
†
163/181
90/ 90
†
86/ 86
90/ 90
†
86/ 86
90/100
†
86/ 87
125/150
†
119/131
175/175
†
144/160
175/200
†
162/181
90/ 90
†
92/ 92
90/ 90
†
92/ 92
100/100
†
92/ 92
150/150
†
125/136
175/175
†
150/165
200/200
†
168/186
—
—
38.0
—
011
38.0
—
011
40.0
70.0
014
63.0
80.0
016
75.0
90.0
016
86.0
—
—
40.0
—
011
40.0
—
011
42.0
70.0
014
65.0
90.0
016
77.0
90.0
016
89.0
—
—
41.0
—
011
41.0
—
011
43.0
70.0
014
66.0
90.0
016
78.0
90.0
016
89.0
—
—
43.0
—
011
43.0
—
011
45.0
80.0
014
68.0
90.0
016
80.0
90.0
016
92.0
90/ 90
†
89/ 89
90/ 90
†
89/ 89
90/100
†
89/ 89
125/150
†
119/131
175/175
†
144/160
175/200
†
162/181
100/100
†
95/ 95
100/100
†
95/ 95
100/100
†
95/ 95
150/150
†
125/136
175/175
†
150/165
200/200
†
168/186
—
—
43.0
—
011
43.0
—
011
43.0
70.0
016
66.0
90.0
016
78.0
90.0
016
89.0
—
—
45.0
—
011
45.0
—
011
45.0
80.0
016
68.0
90.0
016
80.0
90.0
016
92.0
452 + 464 + 455
3
1371
=
3
= 457
7
LRA
465/465
465/465
465/465
465/465
465/465
465/465
469/469
469/469
469/469
469/469
469/469
469/469
488/488
488/488
488/488
488/488
488/488
488/488
493/493
493/493
493/493
493/493
493/493
493/493
233.0
234.0
234.0
234.0
234.0
234.0
235.0
236.0
236.0
236.0
236.0
236.0
245.0
245.0
245.0
245.0
245.0
245.0
247.0
247.0
247.0
247.0
247.0
247.0
550/550
550/550
550/550
550/550
550/550
550/550
555/555
555/555
555/555
555/555
555/555
555/555
260.0
260.0
260.0
260.0
260.0
260.0
262.0
262.0
262.0
262.0
262.0
262.0