Step 5 - Install Flue Hood (48Hj Only); Step 6 - Install Gas Piping (48Hj Only); Step 7 - Install External Trap For Condensate; Drain - Carrier COBRA 48/50HJ004-014 Installation And Service

Energy recovery units
Table of Contents

Advertisement

48HJ004 w/62AQ060
48HJ004 w/62AQ100
48HJ005 w/62AQ060
48HJ005 w/62AQ100
48HJ006 w/62AQ060
48HJ006 w/62AQ100
48HJ007 w/62AQ060
48HJ007 w/62AQ100
50HJ004 w/62AQ060
50HJ004 w/62AQ100
50HJ005 w/62AQ060
50HJ005 w/62AQ100
50HJ006 w/62AQ060
50HJ006 w/62AQ100
50HJ007 w/62AQ060
50HJ007 w/62AQ100
Fig. 6A — Rigging Label — COBRA™ Energy Recovery Unit — Sizes 48/50HJ004-007
Step 5 — Install Flue Hood (48HJ Rooftop Sec-
tions Only) —
Refer to the 48HJ installation instructions for
information on installing the flue hood.
Step 6 — Install Gas Piping (48HJ Rooftop Sec-
tions Only) —
Refer to the 48HJ installation instructions for
information on installing the gas piping.
Step 7 — Install External Trap For Condensate
Drain —
The condensate from the rooftop unit along with
condensate from the upper coil of the energy recovery section
is internally piped to the condensate pan in the lower section of
the energy recovery section. For this reason, the bottom drain
on the rooftop unit CANNOT be used for a condensate drain.
3
The
/
-in. drain connection on the energy recovery section is
4
located near the bottom left of the exhaust air section. See
Fig. 5A and 5B. The energy recovery section must have a
field-fabricated, external, P-trap installed for condensate drain-
age. Trap must be at least 4-in. deep to protect against freeze-
up. If the drain line is installed downstream from the external
MAX WEIGHT
A
lb
kg
in.
mm
890
404
95.6
2428.20
905
411
95.6
2428.20
900
409
95.6
2428.20
915
415
95.6
2428.20
920
418
95.6
2428.20
935
425
95.6
2428.20
995
452
95.6
2428.20
1010
459
95.6
2428.20
795
361
95.6
2428.20
810
368
95.6
2428.20
805
365
95.6
2428.20
820
372
95.6
2428.20
825
375
95.6
2428.20
840
381
95.6
2428.20
880
400
95.6
2428.20
895
407
95.6
2428.20
trap, pitch the line away from the unit at 1-in. per 10-ft of run.
Do not use a pipe smaller than the connection (
Step 8 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA, latest edition, and local electrical
codes. Do not use gas piping as an electrical ground. Fail-
ure to follow this warning could result in the installer being
liable for personal injury of others.
FIELD POWER SUPPLY — All units except 208/230-v
units are factory wired for the voltage shown on the nameplate.
11
B
C
in
mm
in.
mm
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
42.12
1070
57.38
1457.30
42.12
1070
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
33.35
57.38
1457.30
42.12
1070
57.38
1457.30
42.12
1070
847
847
847
847
847
847
847
847
847
847
847
847
3
/
-in.).
4