Table 1D — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ100) (cont)
NOMINAL
IFM
UNIT
V-PH-Hz
TYPE
STD
50HJ006
460-3-60
HIGH STATIC
(cont)
HIGH STATIC
STD
STD
208/230-3-60
HIGH STATIC
HIGH STATIC
50HJ007
STD
STD
460-3-60
HIGH STATIC
HIGH STATIC
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-
cuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent of voltage
imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
HEATER
CONV
62AQ
CRHEATER
OUTLET
FLA
---A00
NONE
006
008
YES
15.1
009
008+008
008+009
NONE
006
008
NO
15.1
009
008+008
008+009
NONE
006
008
YES
15.1
009
008+008
008+009
NONE
002
13.6/15.6
004
21.9/25.3
NO
15.1
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
002
13.6/15.6
004
21.9/25.3
YES
15.1
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
002
13.6/15.6
004
21.9/25.3
NO
15.1
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
002
13.6/15.6
004
21.9/25.3
YES
15.1
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
006
008
NO
15.1
009
008+008
008+009
NONE
006
008
YES
15.1
009
008+008
008+009
NONE
006
008
NO
15.1
009
008+008
008+009
NONE
006
008
YES
15.1
009
008+008
008+009
HEAT
POWER SUPPLY
FUSE OR
FLA
MCA
HACR BKR
—
24.9
30
7.2
24.9
30
13.8
30.9
35
16.8
34.6
40
27.7
48.1
50
30.7
51.9
60
—
23.0
30
7.2
23.0
30
13.8
29.6
35
16.8
33.3
35
27.7
46.8
50
30.7
50.6
60
—
25.7
30
7.2
25.7
30
13.8
31.7
35
16.8
35.4
40
27.7
48.9
50
30.7
52.7
60
—/—
47.9/ 47.9
60/60
47.9/ 47.9
60/60
50.9/ 55.1
60/60
65.2/ 71.6
—
78.2/ 86.7
—
92.6/103.2
—
—/—
53.9/ 53.9
60/60
53.9/ 53.9
60/60
55.7/ 59.3
—
70.0/ 75.8
—
83.0/ 90.9
—
97.4/107.4
—
—/—
49.6/ 49.6
60/60
49.6/ 49.6
60/60
52.6/ 56.8
—
66.9/ 73.3
—
79.9/ 88.4
—
94.3/104.9
—
—/—
55.6/ 55.6
60/60
55.6/ 55.6
60/60
57.4/ 61.0
—
71.7/ 77.5
—
84.7/ 92.6
—
99.1/109.1
—
—
22.8
30
7.2
22.8
30
13.8
28.8
35
16.8
32.5
35
27.7
46.0
50
30.7
49.8
50
—
25.5
30
7.2
25.5
30
13.8
30.9
35
16.8
34.6
40
27.7
48.1
50
30.7
51.9
60
—
23.6
30
7.2
23.6
30
13.8
29.6
35
16.8
33.3
35
27.7
46.8
50
30.7
50.6
60
—
26.3
30
7.2
26.3
30
13.8
31.7
35
16.8
35.4
40
27.7
48.9
50
30.7
52.7
60
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
20
SINGLE
DISCONNECT SIZE*
POINT BOX
CRSINGLE
MOCP
FLA
---A00
—
—
28
—
—
28
—
025
28
—
025
36
—
025
48
—
025
52
—
—
24
—
—
24
—
025
24
—
025
32
—
025
44
—
025
48
—
—
29
—
—
29
—
025
29
—
025
37
—
025
49
—
025
53
—
—
49/ 49
—
—
49/ 49
—
—
49/ 53
70/ 80
002
62/ 68
80/ 90
003
74/ 82
100/110
003
88/ 97
—
—
55/ 55
—
—
55/ 55
70/ 70
002
55/ 58
80/ 80
003
68/ 73
90/100
003
80/ 87
100/110
003
93/102
—
—
51/ 51
—
—
51/ 51
60/ 70
002
51/ 55
70/ 80
002
64/ 70
80/ 90
003
76/ 84
100/110
003
90/ 99
—
—
57/ 57
—
—
57/ 57
70/ 70
002
57/ 60
80/ 80
003
70/ 75
90/100
003
82/ 89
100/110
003
95/104
—
—
23
—
—
23
—
025
23
—
025
31
—
025
43
—
025
47
—
—
29
—
—
29
—
025
29
—
025
36
—
025
48
—
025
52
—
—
24
—
—
24
—
025
24
—
025
32
—
025
44
—
025
48
—
—
30
—
—
30
—
025
30
—
025
37
—
025
49
—
025
53
452 + 464 + 455
3
1371
=
3
= 457
7
457
LRA
119
119
119
119
119
119
123
124
124
124
124
124
128
129
129
129
129
129
260/260
260/260
260/260
260/260
260/260
260/260
265/265
265/265
265/265
265/265
265/265
265/265
279/279
279/279
279/279
279/279
279/279
279/279
284/284
284/284
284/284
284/284
284/284
284/284
127
127
127
127
127
127
131
132
132
132
132
132
136
137
137
137
137
137
141
141
141
141
141
141