NOTE TO INSTALLER:
This manual should be left with the equipment owner.
WARNING: If the information in this manual is
not followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
— Do not store or use gasoline or other flam-
mable vapors and liquids in the vicinity of
this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the
gas supplier.
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
serious injury or death. Refer to this manual. For
assistance or additional information consult a
qualified installer, service agency, or the gas
supplier.
Before performing recommended maintenance, be sure
main power switch to unit is turned off. Electrical shock
could cause serious injury or death.
Your rooftop combination heating/cooling unit is equipped
with an automatic direct spark ignition and induced-draft com-
bustion blower.
Do not attempt to light by hand; serious injury or death
may result.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-80017
Book 1
4
Tab
1a 6a
Single-Package Rooftop
1. Do not turn off the electrical power to unit without
first turning off the gas supply.
2. Before attempting to start the gas heating section,
familiarize yourself with all the procedures that must
be followed.
If you do not follow these instructions exactly, a fire or
explosion may result. Property damage, injury, or loss of
life could occur.
See Fig. 1A and 1B for location of gas valve. Refer to Fig. 2
while proceeding with the following steps.
Step 1 —
setting and set SYSTEM switch to HEAT or AUTO. position.
Step 2 —
Step 3 —
disconnect.
Step 4 —
Step 5 —
and wait 5 minutes.
Step 6 —
Step 7 —
Step 8 —
Step 9 —
Step 10 —
room temperature to start unit. The induced-draft combustion
air fan will start. Main gas valve will open and main burners
should ignite within 5 seconds. If the burners do not light, there
is a 22-second delay before another 5-second try. If the burner
still does not light, the time delay is repeated. If the burner does
not light within 15 minutes, there is a lockout. To reset the con-
trol, break the 24-v power to W1. Repeat Steps 1-10. If burners
still do not light, call for service.
Step 11 —
to desired setting.
If the main burners fail to light, or the blower fails to come
on, shut down gas heating section and call your dealer for
service. Failure to follow these requirements could result in
serious injury or death.
Printed in U.S.A.
Form 48HJ-2SO
48HJ004-014
Heating/Cooling Units
TO LIGHT UNIT
Set room thermostat to the lowest temperature
Close the manual gas valve.
Turn off the electrical supply to the unit, tag
Remove the compressor access panel.
Move the gas valve switch to the OFF position
Move the gas valve switch to the ON position.
Replace the compressor access panel.
Turn on the electrical supply to unit.
Open the manual gas valve.
Set room thermostat selector slightly above
Set the temperature selector on room thermostat
Pg 1
11-00
Replaces: 48GJ,HJ-1SO

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 48HJ004-014

  • Page 1 If the main burners fail to light, or the blower fails to come on, shut down gas heating section and call your dealer for service. Failure to follow these requirements could result in serious injury or death. Printed in U.S.A. Form 48HJ-2SO Pg 1 48HJ004-014 11-00 Replaces: 48GJ,HJ-1SO...
  • Page 2: To Shut Unit Off

    All maintenance should be handled by skilled, experienced personnel. Your Carrier service technician can help you set up a maintenance schedule. For your safety, keep the area around the unit clear and free of combustible materials, gasoline, and other flammable liq- uids and vapors.
  • Page 3 STEP 1 STEP 4 SINGLE-STAGE GAS 2-STAGE GAS VALVE VALVE 48HJD005,006† 48HJD005,006* 48HJE004-006† 48HJE004-006* 48HJF004-006† 48HJF004-006* 48HJG005,006 48HJD007-014 48HJH004-006 48HJE007-014 48HJK004-006 48HJF007-014 48HJL005,006 48HJM004-006 48HJN004-006 STEP 6 STEP 8 *3-phase units only. †Single-phase units only. STEP 2 2-STAGE GAS VALVE 48HJD005,006* 48HJE004-006* 48HJF004-006*...
  • Page 4 STEP 1 2-STAGE GAS VALVE 48HJD005,006* 48HJE004-006* 48HJF004-006* 48HJD007-014 48HJE007-014 48HJF007-014 *3-phase units only. †Single-phase units only. STEP 6 Fig. 3 — To Shut Unit Off STEP 2 STEP 4 SINGLE-STAGE GAS VALVE 48HJD005,006† 48HJE004-006† 48HJF004-006† 48HJG005,006 48HJH004-006 48HJK004-006 48HJL005,006 48HJM004-006 48HJN004-006 STEP 5...
  • Page 5: Routine Maintenance And Care For The Equipment Owner

    ROUTINE MAINTENANCE AND CARE FOR THE EQUIPMENT OWNER Consider the following information before maintaining or servicing equipment: 1. TURN OFF GAS SUPPLY AND THEN ELECTRI- CAL POWER TO YOUR UNIT AND INSTALL LOCKOUT TAG BEFORE SERVICING OR PER- FORMING MAINTENANCE. 2.
  • Page 6 If your unit makes any unusual or especially loud noises during heating, shut down the heating section and call your qualified Carrier service technician. See Fig. 1A, 1B, and 5 and proceed as follows to inspect the combustion area and power-venting system of your unit.
  • Page 7: Regular Dealer Maintenance

    In addition to the type of routine maintenance you might be willing to perform, your unit should be inspected regularly by a properly trained and qualified Carrier service technician. An inspection (preferably each heating/cooling season, but at least every year) should include the following: 1.
  • Page 8: In Case Of Trouble

    Otherwise, you may open the valve and follow the start-up procedures listed in this manual. Copyright 2000 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.