Table 1B — Electrical Data (COBRA™ Energy Recovery 50HJ004-007 Units with 62AQ060) (cont)
NOMINAL
IFM
UNIT
V-PH-Hz
TYPE
STD
50HJ005
460-3-60
HIGH STATIC
(cont)
HIGH STATIC
STD
208/230-1-60
STD
STD
STD
50HJ006
208/230-3-60
HIGH STATIC
HIGH STATIC
STD
460-3-60
STD
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Single point box CRSINGLE017A00 is part of base unit.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-
cuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent of voltage
imbalance.
max voltage deviation from average voltage
= 100 x
average voltage
HEAT
HEATER
CONV
62AQ
CRHEATER
OUTLET
FLA
---A00
NONE
006
YES
9.2
008
009
008+008
NONE
006
NO
9.2
008
009
008+008
NONE
006
YES
9.2
008
009
008+008
NONE
—/—
002
23.5/27.1
003
31.4/36.3
NO
9.2
002+002
46.9/54.2
003+003
62.8/72.5
004+004
75.8/87.5
NONE
—/—
002
23.5/27.1
003
31.4/36.3
YES
9.2
002+002
46.9/54.2
003+003
62.8/72.5
004+004
75.8/87.5
NONE
—/—
002
13.6/15.6
004
21.9/25.3
NO
9.2
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
—/—
002
13.6/15.6
004
21.9/25.3
YES
9.2
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
—/—
002
13.6/15.6
004
21.9/25.3
NO
9.2
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
—/—
002
13.6/15.6
004
21.9/25.3
YES
9.2
005
33.4/38.5
004+004
43.8/50.5
004+005
55.2/63.8
NONE
006
008
NO
9.2
009
008+008
008+009
NONE
006
008
YES
9.2
009
008+008
008+009
POWER SUPPLY
FUSE OR
FLA
MCA
HACR BKR
—
17.9
20
7.2
18.8
25
13.8
27.1
30
16.8
30.8
35
27.7
44.4
45
—
15.6
20
7.2
17.1
20
13.8
25.4
30
16.8
29.1
30
27.7
42.7
45
—
18.3
20
7.2
19.2
25
13.8
27.5
30
16.8
31.2
35
27.7
44.8
45
55.5/ 55.5
70/70
55.5/ 55.5
—
59.5/ 65.5
—
78.9/ 87.9
—
98.7/110.8
—
115.0/129.6
—
61.5/ 61.5
70/70
61.5/ 61.5
—
64.3/ 69.7
—
83.7/ 92.1
—
103.5/115.0
—
119.8/133.8
—
38.1/ 38.1
45/45
38.1/ 38.1
45/45
44.1/ 48.3
50/50
58.4/ 64.9
—
71.5/ 79.9
—
85.8/ 96.4
—
44.1/ 44.1
50/50
44.1/ 44.1
50/50
48.9/ 52.5
60/60
63.2/ 69.1
—
76.3/ 84.1
—
90.6/100.6
—
39.8/ 39.8
45/45
39.8/ 39.8
45/45
45.9/ 50.1
50/60
60.3/ 66.7
—
73.3/ 81.7
—
87.6/ 98.3
—
45.8/ 45.8
50/50
45.8/ 45.8
50/50
50.7/ 54.3
60/60
65.1/ 70.9
—
78.1/ 85.9
—
92.4/102.5
—
—
19.3
25
7.2
19.3
25
13.8
25.4
30
16.8
29.1
30
27.7
42.7
45
30.7
46.4
50
—
22.0
25
7.2
22.0
25
13.8
27.5
30
16.8
31.2
35
27.7
44.8
45
30.7
48.5
50
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
15
SINGLE
DISCONNECT SIZE*
POINT BOX
CRSINGLE
MOCP
FLA
---A00
—
—
21
—
—
21
—
—
21
—
025
32
—
025
44
—
—
16
—
—
16
—
—
19
—
—
28
—
025
40
—
—
22
—
—
22
—
—
22
—
025
32
—
025
45
—
—
56/ 56
70/ 70
004
56/ 56
70/ 70
004
57/ 62
80/ 90
005
75/ 83
100/125
005
93/104
125/150
005
108/121
—
—
61/ 61
70/ 70
004
61/ 61
70/ 70
005
62/ 67
90/100
005
80/ 88
110/125
005
98/109
125/150
005
113/126
—
—
39/ 39
—
—
39/ 39
—
—
42/ 46
60/ 70
002
56/ 62
80/ 80
003
68/ 75
90/100
003
81/ 91
—
—
44/ 44
—
—
44/ 44
—
—
48/ 51
70/ 70
003
61/ 66
80/ 90
003
73/ 80
100/110
003
86/ 95
—
—
41/ 41
—
—
41/ 41
—
—
44/ 48
70/ 70
003
58/ 63
80/ 90
003
70/ 77
90/100
003
83/ 93
—
—
46/ 46
—
—
46/ 46
—
—
50/ 53
70/ 80
003
63/ 68
80/ 90
003
75/ 82
100/110
003
88/ 97
—
—
20
—
—
20
—
—
20
—
—
28
—
025
40
—
025
44
—
—
25
—
—
25
—
—
25
—
025
32
—
025
45
—
025
48
452 + 464 + 455
3
1371
=
3
= 457
7
457
LRA
75
75
75
75
75
84
85
85
85
85
89
90
90
90
90
250/250
250/250
250/250
250/250
250/250
250/250
255/255
255/255
255/255
255/255
255/255
255/255
202/202
202/202
202/202
202/202
202/202
202/202
207/207
207/207
207/207
207/207
207/207
207/207
221/221
221/221
221/221
221/221
221/221
221/221
226/226
226/226
226/226
226/226
226/226
226/226
101
101
101
101
101
101
106
106
106
106
106
106