Hikmicro HM-TD2037T-4/X User Manual
Hikmicro HM-TD2037T-4/X User Manual

Hikmicro HM-TD2037T-4/X User Manual

Automation camera
Hide thumbs Also See for HM-TD2037T-4/X:
Table of Contents

Advertisement

Quick Links

Thermographic Automation Camera
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for Hikmicro HM-TD2037T-4/X

  • Page 1 Thermographic Automation Camera User Manual...
  • Page 2 INTERRUPTION, OR LOSS OF DATA, CORRUPTION OF SYSTEMS, OR LOSS OF DOCUMENTATION, WHETHER BASED ON BREACH OF CONTRACT, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY, OR OTHERWISE, IN CONNECTION WITH THE USE OF THE PRODUCT, EVEN IF HIKMICRO HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OR LOSS.
  • Page 3 Thermographic Automation Camera User Manual PRODUCTION OF CHEMICAL OR BIOLOGICAL WEAPONS, ANY ACTIVITIES IN THE CONTEXT RELATED TO ANY NUCLEAR EXPLOSIVE OR UNSAFE NUCLEAR FUEL-CYCLE, OR IN SUPPORT OF HUMAN RIGHTS ABUSES. IN THE EVENT OF ANY CONFLICTS BETWEEN THIS MANUAL AND THE APPLICABLE LAW, THE LATER PREVAILS.
  • Page 4 Thermographic Automation Camera User Manual Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol Description Indicates a hazardous situation which, if not avoided, will or could Danger result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, Caution could result in equipment damage, data loss, performance...
  • Page 5 Thermographic Automation Camera User Manual Safety Instruction These instructions are intended to ensure that user can use the product correctly to avoid danger or property loss. Laws and Regulations ● In the use of the product, you must be in strict compliance with the electrical safety regulations of the nation and region.
  • Page 6 Thermographic Automation Camera User Manual example, in the case of some lithium battery types). ● DO NOT dispose of the battery into fire or a hot oven, or mechanically crush or cut the battery, which may result in an explosion. ●...
  • Page 7 Thermographic Automation Camera User Manual liquids, such as vases, shall be placed on the equipment. ● No naked flame sources, such as lighted candles, should be placed on the equipment. ● Provide a surge suppressor at the inlet opening of the equipment under special conditions such as the mountain top, iron tower, and forest.
  • Page 8: Table Of Contents

    Thermographic Automation Camera User Manual Contents Chapter 1 Overview........................1 1.1 Brief Description ........................1 1.2 Function ..........................1 Chapter 2 Device Activation and Accessing ................. 2 2.1 Activate the Device via SADP ....................2 2.2 Activate the Device via Browser ................... 2 2.3 Login ............................
  • Page 9 Thermographic Automation Camera User Manual Chapter 6 Live View ........................16 6.1 Live View Parameters ......................16 6.1.1 Window Proportion ....................16 6.1.2 Live View Stream Type ..................... 16 6.1.3 Select the Third-Party Plug-in .................. 16 6.1.4 Enable and Disable Live View .................. 16 6.1.5 Start Digital Zoom ....................
  • Page 10 Thermographic Automation Camera User Manual 7.2.5 Set Palette Range ..................... 24 7.2.6 DDE..........................24 7.2.7 Mirror ........................24 7.2.8 Video Standard ......................25 7.2.9 Local Video Output ....................25 7.3 OSD ............................25 7.4 Overlay Picture ........................25 7.5 Set Manual DPC (Defective Pixel Correction) ..............26 Chapter 8 Video Recording and Picture Capture ................
  • Page 11 Thermographic Automation Camera User Manual 10.6 Upgrade ..........................36 10.7 View Open Source Software License ................36 10.8 Time and Date ........................37 10.8.1 Synchronize Time Manually ................... 37 10.8.2 Set NTP Server ......................37 10.8.3 Set DST ........................37 10.9 Set RS-232 ..........................
  • Page 12: Chapter 1 Overview

    Thermographic Automation Camera User Manual Chapter 1 Overview 1.1 Brief Description The Thermographic Automation Network Camera is a camera with function of high accuracy temperature measurement. With built-in high sensitivity sensor and passive infrared imaging, the camera is able to measure object's temperature from far distance at a high accuracy in bad weather.
  • Page 13: Chapter 2 Device Activation And Accessing

    Thermographic Automation Camera User Manual Chapter 2 Device Activation and Accessing To protect the security and privacy of the user account and data, you should set a login password to activate the device when access the device via network. Note Refer to the user manual of the software client for the detailed information about the client software activation.
  • Page 14: Login

    Thermographic Automation Camera User Manual Note The default IP address of the device is 192.168.1.64. You can set the IP address of the PC from 192.168.1.2 to 192.168.1.253 (except 192.168.1.64). For example, you can set the IP address of the PC to 192.168.1.100. 3.
  • Page 15: Illegal Login Lock

    Thermographic Automation Camera User Manual Operating System Web Browser Operation plug-in installation is not required. Display and operation of certain functions are restricted. For example, Playback and Picture are not available. For detailed restricted function, refer to the actual device. Plug-in installation is not required.
  • Page 16: Chapter 3 Temperature Measurement

    Thermographic Automation Camera User Manual Chapter 3 Temperature Measurement When you enable this function, the device measures the actual temperature of the scene. It alarms when temperature exceeds the temperature threshold value. 3.1 Set Thermography Parameters Configure the parameters of temperature measurement. Steps 1.
  • Page 17: Set Non-Roi Thermography

    Thermographic Automation Camera User Manual improve the temperature measuring accuracy. Calibration Coefficient Check to enable it and set the value of calibration coefficient to get the temperature of the external window or optical material automatically. The setting range is 0 to 30. Note You can get the setting value from SDK software.
  • Page 18: Set Roi Thermometry

    Thermographic Automation Camera User Manual lower/higher than rule temperature by tolerance temperature. For example, set tolerance temperature as 3 °C, set alarm temperature as 55 °C. It alarms when its temperature reaches 55 °C and only when the temperature is below 52 °C will the alarm be canceled. 5.
  • Page 19: Point Thermography

    Thermographic Automation Camera User Manual Area Please refer to Area Thermographyfor detailed configuration. 3. Click and set the Alarm Rule. Alarm Temperature and Pre-Alarm Temperature Set the alarm temperature and pre-alarm temperature. E.g., select Alarm Rule as Above (Average Temperature), set the Pre-Alarm Temperature to 50 °C, and set the Alarm Temperature to 55 °C.
  • Page 20 Thermographic Automation Camera User Manual area. Steps 1. Click and drag the mouse in the liveview to draw the area and right click to finish drawing. 2. Click and move the area to adjust the position. 3. Drag the corners of the area to adjust the size and shape. Go to Live View interface to view the maximum temperature and rule of the area in thermal channel.
  • Page 21: Chapter 4 Event And Alarm

    Thermographic Automation Camera User Manual Chapter 4 Event and Alarm This part introduces the configuration of events. The device takes certain response to triggered alarm. 4.1 Set Alarm Input Alarm signal from the external device triggers the corresponding actions of the current device. Before You Start Make sure the external alarm device is connected.
  • Page 22: Set Burning-Prevention

    Thermographic Automation Camera User Manual 3. Refer to Linkage Method Settings for setting linkage method. 4. Click Save. 4.3 Set Burning-Prevention This function is used to close the shutter to prevent the lens from high temperature damage. Steps 1. Go to Configuration → Event → Basic Event → Burning-Prevention. 2.
  • Page 23: Chapter 5 Arming Schedule And Alarm Linkage

    Thermographic Automation Camera User Manual Chapter 5 Arming Schedule and Alarm Linkage Arming schedule is a customized time period in which the device performs certain tasks. Alarm linkage is the response to the detected certain incident or target during the scheduled time. 5.1 Set Arming Schedule Set the valid time of the device tasks.
  • Page 24: Ftp Uploading

    Thermographic Automation Camera User Manual Manual Alarm You can trigger an alarm output manually. Steps 1. Set the manual alarm parameters. Alarm Output No. Select the alarm output No. according to the alarm interface connected to the external alarm device. Alarm Name Custom a name for the alarm output.
  • Page 25: Send Email

    Thermographic Automation Camera User Manual 5.2.3 Send Email Check Send Email, and the device sends an email to the designated addresses with alarm information when an alarm event is detected. For email settings, refer to Set Email. Set Email When the email is configured and Send Email is enabled as a linkage method, the device sends an email notification to all designated receivers if an alarm event is detected.
  • Page 26: Trigger Recording

    Thermographic Automation Camera User Manual 5.2.5 Trigger Recording Check Trigger Recording, and the device records the video about the detected alarm event. For recording settings, refer to Video Recording and Picture Capture...
  • Page 27: Chapter 6 Live View

    Thermographic Automation Camera User Manual Chapter 6 Live View It introduces the live view parameters, function icons and transmission parameters settings. 6.1 Live View Parameters The supported functions vary depending on the model. 6.1.1 Window Proportion ● refers to the window size is 16 : 9. ●...
  • Page 28: Quick Set Live View

    Thermographic Automation Camera User Manual 2. In live view image, drag the mouse to select the desired region. 3. Click in the live view image to back to the original image. 6.1.6 Quick Set Live View It offers the quick access to the display settings, OSD, and video/audio on live view page. Steps 1.
  • Page 29: Lens Initialization

    Thermographic Automation Camera User Manual 6.1.10 Lens Initialization Lens initialization is used on the device equipped with motorized lens. The function can reset lens when long time zoom or focus results in blurred image. This function varies according to different models.
  • Page 30 Thermographic Automation Camera User Manual The device takes the video fluency as the priority over teal-time. In poor network environment, the device cannot ensures video fluency even the fluency is enabled. 3. Click OK.
  • Page 31: Chapter 7 Video And Audio

    Thermographic Automation Camera User Manual Chapter 7 Video and Audio This part introduces the configuration of video and audio related parameters. 7.1 Video Settings This part introduces the settings of video parameters, such as, stream type, video encoding, and resolution. Go to setting page: Configuration →...
  • Page 32: Video Quality

    Thermographic Automation Camera User Manual compression speed is slower than that of the constant bitrate. But it guarantees the image quality of complex scenes. 7.1.5 Video Quality When Bitrate Type is set as Variable, video quality is configurable. Select a video quality according to actual needs.
  • Page 33: Smoothing

    Thermographic Automation Camera User Manual decoded without any reference to other images. An I-frame consumes more bits than other frames. Thus, video with more I-frames, in other words, smaller I-frame interval, generates more steady and reliable data bits while requiring more storage space. 7.1.8 Smoothing It refers to the smoothness of the stream.
  • Page 34: Display Settings

    Thermographic Automation Camera User Manual Note The higher the ROI level is, the clearer the image of the detected region is. 7. Optional: Select other region No. and repeat the above steps if you need to draw multiple fixed regions. 7.2 Display Settings It offers the parameter settings to adjust image features.
  • Page 35: Set Palette

    Thermographic Automation Camera User Manual Set the DNR level for both space DNR and time DNR to control the noise reduction degree. The higher level means stronger reduction degree. 7.2.4 Set Palette You can select the palette mode to display the thermal grayscale image to colored image. Steps 1.
  • Page 36: Video Standard

    Thermographic Automation Camera User Manual Note The video recording will be shortly interrupted when the function is enabled. 7.2.8 Video Standard Video standard is an ability of a video card or video display device that defines the amount of colors that are shown and the resolution. In PAL, 25 frames are transmitted each second. Each frame is made up of 625 individual scan lines.
  • Page 37: Set Manual Dpc (Defective Pixel Correction)

    Thermographic Automation Camera User Manual 128 pixel. Steps 1. Go to picture overlay setting page: Configuration → Image → Picture Overlay. 2. Click Browse to select a picture, and click Upload. The picture with a red rectangle will appear in live view after successfully uploading. 3.
  • Page 38: Chapter 8 Video Recording And Picture Capture

    Thermographic Automation Camera User Manual Chapter 8 Video Recording and Picture Capture This part introduces the operations of capturing video clips and snapshots, playback, and downloading captured files. 8.1 Set FTP You can configure the FTP server to save images which are captured by events or a timed snapshot task.
  • Page 39: Capture Configuration

    Thermographic Automation Camera User Manual 8.3 Capture Configuration The device can capture the pictures manually or automatically and save them in configured saving path. You can view and download the snapshots. 8.3.1 Capture Automatically This function can capture pictures automatically during configured time periods. Before You Start If event-triggered capture is required, you should configure related linkage methods in event settings.
  • Page 40: Chapter 9 Network Settings

    Thermographic Automation Camera User Manual Chapter 9 Network Settings 9.1 TCP/IP TCP/IP settings must be properly configured before you operate the device over network. Go to Configuration → Basic Configuration → Network → TCP/IP for parameter settings. NIC Type Select a NIC (Network Interface Card) type according to your network condition. IPv4 DHCP The device automatically gets the IPv4 parameters from the network if you check DHCP.
  • Page 41: Port

    Thermographic Automation Camera User Manual 9.2 Port The device port can be modified when the device cannot access the network due to port conflicts. Caution Do not modify the default port parameters at will, otherwise the device may be inaccessible. Go to Configuration →...
  • Page 42: Port Mapping

    Thermographic Automation Camera User Manual 9.3 Port Mapping By setting port mapping, you can access devices through the specified port. Before You Start When the ports in the device are the same as those of other devices in the network, refer to Port to modify the device ports.
  • Page 43: Set Port Mapping On Router

    Thermographic Automation Camera User Manual 9.3.3 Set Port Mapping on Router The following settings are for a certain router. The settings vary depending on different models of routers. Steps 1. Select the WAN Connection Type. 2. Set the IP Address, Subnet Mask and other network parameters of the router. 3.
  • Page 44: Access To Device Via Domain Name

    Thermographic Automation Camera User Manual messages in network transmission. Before You Start Before setting the SNMP, you should download the SNMP software and manage to receive the device information via SNMP port. Steps 1. Go to the settings page: Configuration → Network → Advanced Settings → SNMP. 2.
  • Page 45: Set Open Network Video Interface

    Thermographic Automation Camera User Manual By Client Software Add domain name to the client software. Refer to the client manual for specific adding methods. 9.6 Set Open Network Video Interface If you need to access the device through Open Network Video Interface protocol, you can configure the user settings to enhance the network security.
  • Page 46: Chapter 10 System And Security

    Thermographic Automation Camera User Manual Chapter 10 System and Security It introduces system maintenance, system settings and security management, and explains how to configure relevant parameters. 10.1 View Device Information You can view device information, such as Device No., Model, Serial No. and Firmware Version. Enter Configuration →...
  • Page 47: Restore And Default

    Thermographic Automation Camera User Manual 10.5 Restore and Default Restore and Default helps restore the device parameters to the default settings. Steps 1. Go to Configuration → System → Maintenance → Upgrade & Maintenance. 2. Click Restore or Default according to your needs. Restore Reset device parameters, except user information, IP parameters and video format to the default settings.
  • Page 48: Time And Date

    Thermographic Automation Camera User Manual 10.8 Time and Date You can configure time and date of the device by configuring time zone, time synchronization and Daylight Saving Time (DST). 10.8.1 Synchronize Time Manually Steps 1. Go to Configuration → System → System Settings → Time Settings. 2.
  • Page 49: Set Rs-232

    Thermographic Automation Camera User Manual 3. Select Start Time, End Time and DST Bias. 4. Click Save. 10.9 Set RS-232 RS-232 can be used to debug device or access peripheral device. RS-232 can realize communication between the device and computer or terminal when the communication distance is short.
  • Page 50: Security

    Thermographic Automation Camera User Manual 4. Click Save. 10.12 Security You can improve system security by setting security parameters. 10.12.1 Authentication You can improve network access security by setting RTSP and WEB authentication. Go to Configuration → System → Security → Authentication to choose authentication protocol and method according to your needs.
  • Page 51: Set Ip Address Filter

    Thermographic Automation Camera User Manual 1. Go to Configuration → System → Maintenance → Security Audit Log. 2. Select log types, Start Time, and End Time. 3. Click Search. The log files that match the search conditions will be displayed on the Log List. 4.
  • Page 52 Thermographic Automation Camera User Manual which improves the security of remote access. Steps 1. Go to Configuration → Network → Advanced Settings → HTTPS. 2. Check Enable. 3. Click Delete to recreate and install certificate. Create and install Refer to Create and Install Self-signed Certificate self-signed certificate Create certificate Refer to Install Authorized Certificate...
  • Page 53: Set Qos

    Thermographic Automation Camera User Manual 10.12.6 Set QoS QoS (Quality of Service) can help improve the network delay and network congestion by setting the priority of data sending. Note QoS needs support from network device such as router and switch. Steps 1.
  • Page 54 Thermographic Automation Camera User Manual different user levels. Caution To increase security of using the device on the network, please change the password of your account regularly. Changing the password every 3 months is recommended. If the device is used in high-risk environment, it is recommended that the password should be changed every month or week.
  • Page 55: Chapter 11 Appendix

    0.98 Hard Paperboard 0.90 White Paper 0.90 Water 0.96 11.2 Device Command Scan the following QR code to get device common serial port commands. Note that the command list contains the commonly used serial port commands for Hikmicro thermal cameras.
  • Page 56: Device Communication Matrix

    Thermographic Automation Camera User Manual 11.3 Device Communication Matrix Scan the following QR code to get device communication matrix. Note that the matrix contains all communication ports of Hikmicro thermal cameras. 11.4 FAQ Q: How to integrate SDK? Refer to user manual of SDK software. Please contact the technical person.
  • Page 57 UD23897B...

This manual is also suitable for:

Hm-td2037t-7/xHm-td2037t-10/xHm-td2067t-6/x

Table of Contents