Transmitter Module (4XTMF)
For Local Energy Municipal Box service (NFPA 72-1993 Auxiliary Fire Alarm System):
Supervisory current: 5.0 mA.
Trip current: 0.35 amps. (Subtracted from Notification Appliance power.)
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building.
For Remote Station service (NFPA 72-1993 Remote Station Fire Alarm System):
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
LED Interface Module (4XLMF)
Maximum voltage/current, each output: 27.6V/8mA.
Note: Outputs are power limited.
Zone Relay Module (4XZMF)
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
1.4

Remote Annunciator

Notifier Remote Annunciator (RZA-4XF)
The Remote Annunciator mounts on a standard single-gang box, and provides
LED indication of the same functions as the zone relay module. For example,
with DIP 1=ON and DIP 2=OFF:
• One Zone in Alarm (red)
• Two Zones in Alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring
is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate.
Note: The Remote Annunciator requires the use of an LED Interface module
(4XLMF).
1.5

Optional Meters

Voltage, Current Meters (4XMMF)
The Meter Module provides a voltmeter to measure the voltage across the
batteries and an ammeter to measure the charging current to the batteries.
The meters are provided as a assembly that mounts to the lower left-hand
corner of the cabinet.