Required Reprogramming Of Tracer Adaptiview Controls; Reprogramming Retrofit Tracer Adaptiview Controls (Cvr Firmware) - Trane CVHE Installation Instructions Manual

Afdh d-frame retrofit adaptive frequency drive for ucp2, tracer ch531, and tracer adaptiview centrifugal chiller controllers
Table of Contents

Advertisement

Installation
Required Reprogramming of
Tracer AdaptiView Controls
Reprogramming Retrofit Tracer
AdaptiView Controls (CVR Firmware)
Important:
For a chiller retrofitted with an AFDH drive to operate
correctly and efficiently, it is critical that the actual
specific nameplate data values for the chiller be
entered in the UC800 menu parameters listed in the
table below (i.e. motor data and compressor impeller
data). If the unit nameplate is missing, unreadable, or
of a vintage that did not include all of the required data
categories, contact Trane Global Parts Technical
Table 16. UC800/Tracer AdaptiView CVR parameter values with a retrofit AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
AF Control
ReOptimization Sensitivity
Tracer TU Field Startup View:
Adjustable Frequency Drive
Maximum Frequency
Minimum Frequency
AFD Surge Capacity Increase
Tracer TU Configuration View:
Main
Unit Type (MODL)
Starter Type
Tracer TU Configuration View:
UC800
Impeller Diameter (CPIM)
Number of Stages
Tracer TU Configuration View:
Starter
Stop Delay Time (Contactor Interrupt
Failure)
Unit Voltage
Voltage Transformer Ratio
Rated Load Amps (RLA)
CT Meter Scale
Current Unbalance Trip Point
Current Unbalance Grace Period
Maximum Acceleration Setting
Acceleration Time Out Action
Overload Type
Phase Reversal
Contactor Integrity Test
Phase Reversal Grace Period
Surge Protection
Momentary Power Loss
Restart Inhibit Stop to Start Time
Surge Sensitivity
Power Loss Reset Time
40
Note: CVR MP firmware is always used in the UC800 on
Range
Default Setting
Auto, Fixed
0–100%
Range
Default Setting
38–60 Hertz
38–60 Hertz
0–5%
Range
Default Setting
Not Applicable
Not Applicable
Not Applicable
Wye-Delta
Range
Default Setting
210–335
CVHE = 3, CVHF = 2
Range
Default Setting
1–30 Seconds
180–15000 Volts
0–700
0–2500 Amps
0–2000
15–100%
10–255 Seconds
6–64 Seconds
Shutdown, Transition
Shutdown
Exponential, Linear
Enable, Disable
Enable, Disable
20–1000 milliseconds
Enable, Disable
Enable, Disable
0–255 Seconds
0–100%
0–255 Seconds
Services. To contact them, send a message to
ATechnicalService@trane.com. Provide the chiller
serial number and request a copy of the shipped-with
bill of materials for this unit.
Make sure your laptop is loaded with the most current
version of Tracer® TU tool software so that you have
the most up-to-date version of CVR MP firmware
available to install into the UC800.
Tracer® AdaptiView™ control systems or display
upgrades that were retrofitted in place of all earlier
versions of chiller controllers with only one specific
exception: factory-installed CH530 controls.
Factory-installed CH530 control systems used CTV
MP firmware so the new Tracer® AdaptiView™
controls will also use CTV MP firmware.
Recommended Setting
Auto
20
Recommended Setting
60
38
1
Recommended Setting
Recommended Setting
275
Enter CPIM from Unit Nameplate
2
Enter from Unit Nameplate
Recommended Setting
3
460
Enter from Unit Nameplate
20
Enter from Unit Nameplate
500
Enter from Unit Nameplate
0
Choose Correct CT Meter Scale from
30
90
6
Linear
Enable
Disable
700
Enable
Enable
30
20
15
Auto
20
60
38
1
CVR
Non-Comm AFD
30
Table 15, p. 39
30
90
30
Shutdown
Linear
Disable
Disable
1000
Enable
Disable
60
20
15
AFDH-SVN03H-EN