There has been a tendency with installers to change this
setting to the "North America" setting. The preset
parameters are "Motor Power in KW based." Changing
[0-03 Regional Settings] to "North America" will change
the drive to "Motor Power in HP based." This will reset
all of the presets to the default settings. If this
occurs all of the presets must be reprogrammed.
Table 18. Job specific settings
Group Parameter Description
1
20
Motor Kw
1
24
Motor Current
1
25
Motor Nominal speed
4
16
Torque limit mode
4
18
Current limit
Refer to
Table 19
for a list of items that are programmed in
the drive at the factory for use with Trane® chillers. In the
event that the drive needs to be reset, these parameters
need to be reprogrammed into the drive.
To reset the drive to the Danfoss defaults, perform the
following procedure.
1. Disconnect power to the drive, and wait for the display
to shut down.
2. While powering up the drive, press and hold the
following keys: Status, Main, and OK.
3. AFter 5 seconds, release the keys.
After the drive is reset, reprogram the items listed in
Table
19.
These parameters are supposed to have been set at the
factory to the Trane specific values shown here in
Always confirm before actual drive start up that this is so
and correct any one of the parameter settings as
necessary.
Table 19. Trane default settings
Group Parameter Description
0
20
Display line 1.1 small
0
21
Display line 1.2 small
0
22
Display line 1.3 small
0
23
Display line 2 large
0
24
Display line 3 large
0
40
Hand on key
0
41
Off key
0
60
Main Menu password
0
61
Access to main menu
without password
1
03
Torque characteristics
1
22
Motor voltage
1
23
Motor frequency
AFDH-SVN03H-EN
Table 19. Trane default settings (continued)
Group Parameter Description
1
1
1
3
3
3
Value
Set to nameplate
4
CPKW
4
Set to nameplate
5
TVA (or FLA)
Set to nameplate
(a)
5
RPM
6
Set to maximum
6
Set to maximum
6
6
6
14
14
(a) There are actually 2 relays under 5 - 40 (Relay 1 and Relay 2). When
Table
19.
Setting
DC link voltage
(1630)
Analog input (1662)
Heat sink temp
(1634)
Power Kw (1610)
Freq Hz (1613)
Disabled (0)
Disabled (0)
999
Read only (1)
Variable torque (1)
Nameplate voltage
60 Hz
AFDH Startup Procedure
39
Motor poles
71
Start delay
73
Flying start
03
Maximum Reference
41
Ramp 1 ramp up time 10 sec
42
Ramp 1 ramp down
time
12
Motor speed low limit
14
Motor speed high limit 60 Hz
12
Terminal 27 digital
input
40
Function Relay
10
Terminal 53 low voltage 2 volts
14
Terminal 53 low
Ref./Feedb value
15
Terminal 53 High
Ref./Feedb. value
17
Terminal 53 live zero
27
Terminal 54 live zero
20
Reset Mode
21
Automatic Restart Time 60 sec.
entering 5 - 40 the required setting on Relay 1 = Alarm (9) as shown
here but then you need to scroll down to Relay 2 and confirm that Relay
2 = Run (5). The relays are NOT interchangeable. Relay 1 must always
be set to Alarm (9). Relay 2 must always be set to Run (5).
Setting
Poles (2)
0.5
Disabled
60 Hz
20 sec
38 Hz
Coast inverse (2)
Alarm (9)
38 Hz
60 Hz
Disable
Disable
Automatic reset x 5
43