Remote Mount Weights and Heat
Rejection
Table 8.
AFDH D-Frame remote mount unit weights (460 V/480 V)
460 V/V480 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 9.
AFDH D-Frame remote mount unit weights (380 V/400 V)
380 V/400 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
Table 10. AFDH D-Frame remote mount unit weights (575 V/600 V)
575 V/600 V D-Frame AFDH
(a)
Catalog/Maximum
Amps
Unit Weight
Heat Rejection
(a) Catalog amps reflect nominal selection sizes, maximum amps reflect AFD maximum capacity. Applications beyond catalog amps are allowed per dis-
cussions with product support team.
AFDH-SVN03H-EN
281 Catalog/
336 Catalog/
301 Maximum
361 Maximum
652 lb
14,300 Btu/h
293 Catalog/
367 Catalog/
315 Maximum
395 Maximum
652 lb
14,300 Btu/h
178 Catalog/
226 Catalog/
192 Maximum
242 Maximum
652 lb
695 lb
11,262 Btu/h
14,300 Btu/h
AFDH Drive Package Specifications
413 Catalog/
443 Maximum
695 lb
767 lb
16,380 Btu/h
19,800 Btu/h
446 Catalog/
480 Maximum
695 lb
767 lb
16,380 Btu/h
19,800 Btu/h
271 Catalog/
290 Maximum
695 lb
16380 Btu/h
500 Catalog/
535 Maximum
1088 lb
24,450 Btu/h
545 Catalog/
588 Maximum
1088 lb
24,450 Btu/h
321 Catalog/
374 Catalog/
344 Maximum
400 Maximum
767 lb
1088 lb
19,800 Btu/h
24,450 Btu/h