Connect Wiring

1. Pull all required wiring (data+, data-) into the back box. As needed,
pull an additional ESD ground wire (required only when the station is
not installed in grounded metal conduit).
2. Connect the station ESD ground wire pigtail.
a. Strip 11 mm (7/16 in) of insulation from the ends of the station
b. Use one WAGO connector, provided in the termination kit, to
c. Install the ESD ground wire pigtail FASTON connector to the
3. Terminate EchoConnect wires. EchoConnect is topology free; you may
install the wires in any combination of bus, star, loop, or home-run.
a. Strip 11 mm (7/16 in) from the ends of each power pigtail wire
b. Use the provided WAGO connectors to connect the power pigtail
c. Install the two-pin connector from the power pigtail to the
Echo Inspire Station
When using Category 5 (or equivalent) cable on the
Cat5 wiring must be terminated using EchoConnect Cat5
Termination Kit and must be installed using a bus topology.
Refer to the installation guide that is provided with the Cat5
Termination Kit (7186A1207) for information to terminate
Cat5 wiring.
Not all topologies are supported using Cat5; careful planning
is required to ensure the proper termination kits are available
and the wire is pulled appropriately.
ground wire pigtail, provided in the termination kit, and the
incoming ground wire.
connect the station ESD ground pigtail and the incoming ground.
For stations using grounded metal conduit, connect the ground
pigtail to the metal back box ground location.
mating receptacle on the station electronics.
provided in the termination kit and the installed control wires.
wires and the installed Belden 8471 control wires. One WAGO
should be used for the white wire pair (data +) and one for the
black wire pair (data -). Open the terminal levers on the WAGO
connector and insert the installed Belden 8471 wire and the lead
from the power pigtail into the terminals, and then close the
levers.
mating receptacle on the station electronics.