3–32
Func.
Code
C31
Terminal 11 active
state
C32
Terminal 12 active
state
C33
Alarm relay active
state
Option
Code
00
01
02
03
04
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
"C" Group: Intelligent Terminal Functions
The output logic convention is programmable for terminals 11 and 12. The open-collec-
tor output terminals 11 and 12 default to normally open (active low), but you can select
normally closed (active high) for terminals 11 and 12 in order to invert the sense of the
logic.
"C" Function
Name
Select logic convention, two
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
Select logic convention, two
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
Select logic convention, two
option codes:
00 ...normally open [NO]
01 ...normally closed [NC]
Summary Table - this table shows all six functions for the logical outputs (11, 12) at a
glance. Detailed descriptions of these functions, related parameters and settings, and
example wiring diagrams are in Chapter 4, starting on page 4–18.
Output Function Summary Table
Terminal
Function Name
Symbol
RUN
Run signal
FA1
Frequency arrival
type 1 signal
FA2
Frequency arrival
type 2 signal
OL
Overload advance
notice signal
OD
Output deviation for
PID control
Run-
time
Description
Edit
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
ON
when output to motor is at the set frequency
OFF
when output to motor is off, or in any accelera-
tion or deceleration ramp
ON
when output to motor is at or above the set
frequency, even if in accel. or decel. ramps
OFF
when output to motor is off, or at a level below
the set frequency
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold
for the overload signal
ON
when PID error is more than the set threshold for
the deviation signal
OFF
when PID error is less than the set threshold for
the deviation signal
Defaults
DOP,DRW,DOP+
EU/
Func.
Units
US
Code
00
F-35
OUT-TM
O/C-1
00
F-35
OUT-TM
O/C-2
01
F-35
OUT-TM
O/C-RY
Description