Analog Input Current/Voltage Select
Option
Code
16
Valid for inputs:
Required settings:
Notes:
If the [AT] option is not assigned to any intelligent
input terminal, then inverter uses the algebraic sum
of both the voltage and current inputs for the
frequency command (and A01=01).
When using either the analog current and voltage
input terminal, make sure that the [AT] function is
allocated to an intelligent input terminal.
Be sure to set the frequency source setting A01=01
to select the analog input terminals.
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input
terminals for external frequency control. When the switch between the terminals [AT]
and [P24] is on, it is possible to set the output frequency by applying a current input
signal at [OI]-[L]. When the terminal is turned off, the voltage input signal at [O]-[L] is
available. Note that you must also set parameter A1 = 01 to enable the analog terminal
set for controlling the inverter frequency.
Terminal
Function Name
Symbol
AT
Analog Input
Voltage/current
Select
C01, C02, C03, C04, C05
A01 = 01
Input
Description
State
ON
Terminal OI is enabled for current input (uses
terminal L for power supply return)
OFF
Terminal O is enabled for voltage input (uses
terminal L for power supply return)
Example:
AT
L
5
H
O
OI
L
+ –
See I/O specs on page 4–5.
4–15
L100 Inverter
P24
4
3
2
1
FM
CM2
12
11
4-20 mA when AT= On
0-10 V when AT= Off