3–12
Multi-speed Frequency Setting
Func.
Code
A20
Multi-speed
frequency setting
A21
Multi-speed
to
frequency settings
A35
A38
Jog frequency setting
A39
Jog stop mode
Toll Free: voice: 1-877-539-2542 fax: 1-800-539-2542 www.mgitech.com
Technologies Inc.
"A" Group: Standard Functions
The L100 inverter has the capability to store and output up to 16 frequencies to the
motor (A20 to A35). As in traditional motion terminology, we call this multi-speed
profile capability. Binary-encoded logic inputs select the particular frequency (speed)
setting, and the inverter applies the current acceleration or deceleration setting required
to change from the current output frequency to the new one.
The jog speed setting is used whenever the Jog command is active. The jog speed setting
range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The
acceleration to the jog frequency is instantaneous, but you can choose from three modes
for the best method for stopping the jog operation.
"A" Function
Name
Defines the first speed of a
multi-speed profile, range is
0 to 360 Hz
Defines 15 more speeds,
range is 0 to 360 Hz.
A21 = Speed 2...
A35 = Speed 16
Defines limited speed for jog,
range is 0.5 to 9.99 Hz
Define how end of jog stops
the motor; three options:
00 ...Free-run stop
01 ...Controlled deceleration
02 ...DC braking to stop
Run-
time
Description
Edit
Defaults
DOP,DRW,DOP+
EU/
Func.
Units
Name
US
Code
0
Hz
F-11
SPD FS
0 (all)
Hz
F-11
SPD 1
to
SPD 15
1.0
Hz
Mon.
JOGGING
00
Mon.
JOG
MODE