APPENDIX D
Voltage Compensation Chart
Refresh /
°C
Float
Equalize
>35
2.230
2.380
34
2.232
2.382
33
2.234
2.384
32
2.236
2.386
31
2.238
2.388
30
2.240
2.390
29
2.242
2.392
28
2.244
2.394
27
2.246
2.396
26
2.248
2.398
25
2.250
2.400
24
2.252
2.402
23
2.254
2.404
22
2.256
2.406
21
2.258
2.408
20
2.260
2.410
19
2.262
2.412
18
2.264
2.414
17
2.266
2.416
16
2.268
2.418
15
2.270
2.420
14
2.272
2.422
13
2.274
2.424
12
2.276
2.426
11
2.278
2.428
<10
2.280
2.430
2mV per ºC
Standby (Float) Application Charge Current Limits Non-Interlock
AVR45 Series
°F
Max. Charge
Cell Type
Current (A)
>95
AVR45-5
93.2
AVR45-7
91.4
AVR45-9
89.6
AVR45-11
87.8
AVR45-13
86.0
AVR45-15
84.2
AVR45-17
82.4
AVR45-19
80.6
AVR45-21
78.8
AVR45-23
77.0
AVR45-25
75.2
AVR45-27
73.4
AVR45-29
71.6
AVR45-31
69.8
AVR45-33
68.0
66.2
AVR95 Series
64.4
Max. Charge
62.6
Cell Type
Current (A)
60.8
AVR95-7
59.0
AVR95-9
57.2
AVR95-11
55.4
AVR95-13
53.6
AVR95-15
51.8
AVR95-17
<50
AVR95-19
AVR95-21
AVR95-23
AVR95-25
AVR95-27
AVR95-29
AVR95-31
AVR95-33
** = Using minimum charge current will extend recharge time and increase risk of battery being undercharged
Min. Charge
Current (A)**
16.5
4.9
24.7
7.4
32.9
9.9
41.1
12.3
49.4
14.8
57.6
17.3
65.8
19.7
74.1
22.2
82.3
24.7
90.5
27.2
98.7
29.6
107
32.1
115
34.6
123
37.0
132
39.5
Min. Charge
Current (A)**
51.5
15.4
68.7
20.6
85.8
25.7
103
30.9
120
36.0
137
41.2
154
46.3
172
51.5
189
56.6
206
61.8
223
66.9
240
72.1
257
77.2
275
82.4
b.26
AVR75 Series
Max. Charge
Cell Type
Current (A)
AVR75-5
27.3
AVR75-7
41.0
AVR75-9
54.6
AVR75-11
68.3
AVR75-13
81.9
AVR75-15
95.6
AVR75-17
109
AVR75-19
123
AVR75-21
137
AVR75-23
150
AVR75-25
164
AVR75-27
177
AVR75-29
191
AVR75-31
205
AVR75-33
218
Min. Charge
Current (A)**
8.2
12.3
16.4
20.5
24.6
28.7
32.8
36.9
41.0
45.0
49.1
53.2
57.3
61.4
65.5