8. Pull cell from module onto lifting device. Care should be taken
so lifting device does not come in contact with cell posts.
Cell Replacement Procedure
1. Cells develop internal pressure. Relieving this pressure from the
cell will make it easier to install the cell into the module. Follow the
steps of "Cell Removal Procedure" item 4.
2. Ensure cell polarity is correct prior to installing cell
3. Replace cell retainer bar.
4. Refer to "Electrical Connection" section for installing connectors of
replacement cell.
b.22