APPENDIX A — WSHP OPEN SCREEN CONFIGURATION
SCREEN NAME
POINT NAME
Operating Mode
SPT
SAT
Condenser Leaving
Temperature
Condenser Entering
Temperature
Fan
Equipment
Compressor Capacity
Status
Damper Position
H
O Economizer
2
Auxiliary Heat
Space RH
Dehumidification
IAQ CO
SPT Alarm Status
Alarming SPT
SPT Alarm Limit
SPT Sensor Alarm
Status
IAQ Alarm Status
Compressor Alarm
Alarm Status
Status
SAT Alarm Status
Condensate Overflow
Alarm Status
Condenser Water Tem-
perature Alarm Status
Filter Alarm Status
Space RH Alarm Status
OAT Alarm Status
Airside Linkage Status
Condenser Water
Linkage
SAT
SAT Offset
Leaving Condenser
Water Temperature
Leaving CW Offset
Sensor
Calibration
Rnet Sensor
Temperature
Rnet Offset
RH
RH Sensor Offset
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI
— Third Party Integration
PASSWORD
EDITABLE
LEVEL
No Password
Required
2
No Password
Required
X
X
Admin Password
level access only
X
X
RANGE
DEFAULT
Off, Fan Only, Economize,
Cooling, Heating, Cont Fan,
Test, Start Delay, Dehumidify
F
F
F
F
Off/Low Speed/
Medium Speed
High Speed/On
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 - 100%
Inactive/Active
0 - 9999 ppm
Normal/Alarm
F
F
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
Normal/Alarm
F
-9.9 - 10.0 F
0 F
F
-9.9 - 10.0
F
0 F
F
-9.9 - 10.0
F
0 F
%
-15% - 15%
54
NOTES
Displays unit operating mode
Displays SPT
Displays SAT
Displays leaving condenser
water temperature
Displays entering condenser
water temperature (Value
will not update when compressor
is operating)
Displays fan speed status
Displays compressor capacity
Displays current damper position
(Viewable only if Ventilation DMP
Type = 2 position or DCV)
Displays position of economizer valve
Displays position of auxiliary
reheat valve (Viewable only if Leaving
Air Auxiliary Heat Type = 2 position,
1 stage Elect or Modulating)
Displays space RH% (Viewable only if
Humidity Sensor = Installed)
Displays if dehumidification is active
(Viewable only if Factory
Dehumidification Reheat = Installed)
Displays the space CO
Displays current space
temperature condition
Displays the SPT that
exceeded the alarm limit (when SPT
alarm above is in Alarm)
Displays the SPT alarm limit that was
exceeded; causing the alarm condition
(when SPT alarm above is in Alarm)
Displays the status of the Rnet
SPT sensor - ALARM is displayed
should the sensor fail to communicate
with the control module
Current IAQ/ventilation condition
Current compressor condition
Current SAT condition
Current status of the condensate
drain (overflow switch)
Current status of the
condenser water
Current filter condition
Current space RH condition
Current status of the OAT
broadcast function
Current linkage status if enabled
Current linkage status if enabled
Display SAT
Used to correct sensor reading
Displays Leaving Condenser
Water Temperature
Used to correct sensor reading
Displays SPT
Used to correct sensor reading
Displays Space RH value
0 %
Used to correct sensor reading
level
2