Wshp Open Test Mode; Retry Mode; Aquazone Deluxe D Control Led Indicators - Carrier AQUAZONE 50PTH Installation And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

WSHP Open Test Mode —
mode, navigate from the BACview
uration screen. Choose the service screen and enable unit test.
The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to
high, and operates each speed for one minute. Resets to disable
on completion.
COMPRESSOR TEST — Tests compressor cooling and
heating operation. Sequences cooling stage 1 then cooling
stage 2 followed by heating stage 2 then reduces capacity to
heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification
mode. Operates for 2 minutes.
AUXILIARY HEATING TEST — Tests
Sequences fan on and enables heating coil for 1 minute.
H
O ECONOMIZER TEST — Tests entering/returning
2
water loop economizer operation. Sequences fan and opens
economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air
(OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper
actuator to set proper preload.
NOTE: The auxiliary heating test, H
vent damper 100% test, and preposition OA damper features
will not be visible on the screen unless configured.
Table 29 — Aquazone Deluxe D Control Current LED Status and Alarm Relay Operations
DESCRIPTION
Normal Mode
Normal Mode with PM
Deluxe D Control
is non-functional
Test Mode
Night Setback
ESD
Invalid T-stat Inputs
No Fault in Memory
HP Fault
LP Fault
FP1 Fault
FP2 Fault
CO Fault
Over/Under Voltage
HP Lockout
LP Lockout
FP1 Lockout
FP2 Lockout
CO Lockout
LEGEND
CO
— Condensate Overflow
ESD — Emergency Shutdown
FP
— Freeze Protection
To enter WSHP Open test
6
home screen to the config-
auxiliary
heat.
O economizer test, open
2
STATUS LED
TEST LED
(Green)
(Yellow)
On
Off
On
Off
Off
Off
On
Flashing Code 2
Flashing Code 3
Flashing Code 4
On
Off
Slow Flash
Off
Slow Flash
Off
Slow Flash
Off
Slow Flash
Off
Slow Flash
Off
Slow Flash
Off
Fast Flash
Off
Fast Flash
Off
Fast Flash
Off
Fast Flash
Off
Fast Flash
Off
HP
— High Pressure
LP
— Low Pressure
PM
— Performance Monitor
Once tests are complete, set unit test back to disable. Unit will
automatically reset to disable after 1 hour.
In Retry mode, the status LED will start to
Retry Mode —
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat used to terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Aquazone™ Deluxe D Control LED Indica-
There are 3 LED indicators on the Deluxe D control:
tors —
STATUS LED — Status LED indicates the current status or
mode of the D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the D
control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will
always flash a code representing the last fault in memory. If
there is no fault in memory, the fault LED will flash code 1 and
appear as one fast flash alternating with a 10-second pause.
See Table 29.
FAULT LED (Red)
Flash Last Fault Code in Memory
Flashing Code 8
Off
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flash Last Fault Code in Memory
Flashing Code 1
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
Flashing Code 7
Flashing Code 2
Flashing Code 3
Flashing Code 4
Flashing Code 5
Flashing Code 6
NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: "Flashing Code 2" is represented by 2 fast flashes
followed by a 10-second pause. This sequence will repeat con-
tinually until the fault is cleared.
43
ALARM RELAY
Open
Cycle (closed 5 sec,
open 25 sec, ...)
Open
Cycling Appropriate Code
Open
Open
Open
Open
Open
Open
Open (closed after 15 minutes)
Closed
Closed
Closed
Closed
Closed

Hide quick links: