Step 8 - Wire Field Power Supply - Carrier AQUAZONE 50PTH Installation And Service Instructions Manual

Two-stage water source heat pumps with puron refrigerant (r-410a)
Table of Contents

Advertisement

CONDITION
Scaling Potential — Primary Measurement
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.
pH/Calcium
Hardness Method
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be
implemented.
Ryznar Stability Index
Langelier Saturation Index
Iron Fouling
2+
Iron Fe
(Ferrous)
(Bacterial Iron Potential)
Iron Fouling
Corrosion Prevention††
pH
Hydrogen Sulfide (H
S)
2
Ammonia Ion as Hydroxide,
Chloride, Nitrate and Sulfate
Compounds
Maximum Chloride Levels
Erosion and Clogging
Particulate Size and Erosion
Brackish
LEGEND
HWG —
Hot Water Generator
HX
Heat Exchanger
N/A
Design Limits Not Applicable Considering Recirculating
Potable Water
NR
Application Not Recommended
SS
Stainless Steel
*Heat exchanger materials considered are copper, cupronickel, 304 SS
(stainless steel), 316 SS, titanium.
†Closed recirculating system is identified by a closed pressurized piping
system.
**Recirculating open wells should observe the open recirculating design
considerations.
Table 3 — Metal Hose Minimum Bend Radii
HOSE DIAMETER (in.)
1
/
2
3
/
4
1
Rib Crimped
Length
(2 ft Length Standard)
Fig. 14 — Supply/Return Hose Kit
Table 2 — Water Quality Guidelines
HX
CLOSED RECIRCULATING†
MATERIAL*
All
N/A
All
N/A
All
N/A
All
N/A
All
N/A
6 - 8.5
All
Monitor/treat as needed.
All
N/A
All
N/A
Copper
N/A
Cupronickel
N/A
304 SS
N/A
316 SS
N/A
Titanium
N/A
<10 ppm of particles and a
maximum velocity of 6 fps.
All
Filtered for maximum
800 micron size.
All
N/A
MINIMUM BEND RADII (in.)
1
2
/
2
4
1
5
/
2
Swivel
Brass
Brass
Fitting
Fitting
MPT
OPEN LOOP AND RECIRCULATING WELL**
pH < 7.5 and Ca Hardness, <100 ppm
If >7.5 minimize steel pipe use.
If <–0.5 minimize steel pipe use.
Based upon 150 F HWG and direct well, 85 F indirect well HX.
<0.2 ppm (Ferrous)
2+
If Fe
(ferrous) >0.2 ppm with pH 6 - 8, O
<0.5 ppm of Oxygen
Above this level deposition will occur.
Minimize steel pipe below 7 and no open tanks with pH <8.
At H
S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.
2
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.
Maximum allowable at maximum water temperature.
50 F (10 C)
<20 ppm
<150 ppm
<400 ppm
<1000 ppm
>1000 ppm
<10 ppm (<1 ppm "sandfree" for reinjection) of particles and a maximum velocity
of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not
removed can potentially clog components.
Use cupronickel heat exchanger when concentrations of calcium or sodium chlo-
ride are greater than 125 ppm are present. (Seawater is approximately 25,000
ppm.)
††If the concentration of these corrosives exceeds the maximum allowable
level, then the potential for serious corrosion problems exists.
Sulfides in the water quickly oxidize when exposed to air, requiring that no
agitation occur as the sample is taken. Unless tested immediately at the
site, the sample will require stabilization with a few drops of one Molar zinc
acetate solution, allowing accurate sulfide determination up to 24 hours
after sampling. A low pH and high alkalinity cause system problems, even
when both values are within ranges shown. The term pH refers to the acid-
ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid-
ered to be acidic. Above 7.0, water is considered to be basic. Neutral water
contains a pH of 7.0.
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is
equivalent to ppm.
Step 8 — Wire Field Power Supply
To avoid possible injury or death due to electrical shock,
open the power supply disconnect switch and secure it in
an open position during installation.
Use only copper conductors for field-installed electrical
wiring. Unit terminals are not designed to accept other
types of conductors.
All field-installed wiring, including the electrical ground,
MUST comply with the National Electrical Code (NEC) as
well as applicable local codes. In addition, all field wiring must
12
6.0 - 7.5
–0.5 to +0.5
<5 ppm check for iron bacteria.
2
6 - 8.5
<0.5 ppm
<0.5 ppm
75 F (24 C)
100 F (38 C)
NR
NR
NR
NR
<250 ppm
<150 ppm
<550 ppm
<375 ppm
>550 ppm
>375 ppm
WARNING
CAUTION