APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME
POINT NAME
SPT Occupied Alarm
Hysteresis
SPT Alarm Delay
SPT Unoccupied Low
Alarm Temperature
SPT Unoccupied High
Alarm Temperature
SAT Low SAT
Alarm Limit
SAT High SAT
Alarm Limit
Condensate Overflow
Alarm Delay
Space Humidity Occupied
High Alarm Limit
Space Humidity Alarm

Configuration

Delay
Space Humidity Unoccu-
pied High Alarm Limit
Alarm
IAQ/Ventilation Occupied
Configuration
High Alarm Limit
IAQ/Ventilation
Alarm Delay
Rnet Sensor SPT Alarm
Rnet Sensor SAT Alarm
Rnet Sensor Compressor
Lockout Alarm
Rnet Sensor Condenser
Water Temperature Alarm
Rnet Sensor Condensate
Overflow Alarm
Rnet Sensor Dirty
Filter Alarm
Rnet Sensor Space
High Humidity Alarm
Loop Control Network
Configuration
Number
Loop Control Network
Address
Number of Linked Heat
Linkage
Pumps
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT
— Supply Air Temperature
SPT — Space Temperature
TPI
— Third Party Integration
PASSWORD
EDITABLE
LEVEL
X
X
X
X
X
X
X
X
X
Admin Password
X
level access only
X
X
X
X
X
X
X
X
X
59
RANGE
DEFAULT
2 - 20 F
5 F
0 - 30 min per degree
10 min
35 - 90 F
45 F
45 - 100 F
95 F
15 - 90 F
45 F
90 - 175 F
120 F
5 - 600 sec
10 sec
45% - 100%
100%
0 - 30 min per % RH
5 min
45% - 100%
100%
0 - 9999 ppm
1100 ppm
0.1 - 1.0 min per ppm
0.25 min
Ignore/Display
Ignore
Ignore/Display
Ignore
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Display
Ignore/Display
Ignore
NOTES
Defines the hysteresis applied above
the cooling and below the heating set
points before an alarm condition will
occur
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Defines the fixed unoccupied
ow SPT alarm limit
Defines the fixed unoccupied
high SPT alarm limit
Defines the fixed minimum
SAT alarm limit
Defines the fixed maximum
SAT alarm limit
Defines the delay time before an alarm
is generated after the alarm condition
occurs
Defines the fixed occupied
high space RH alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Defines the fixed unnoccupied
high space RH alarm limit
Defines the fixed occupied high
space IAQ/Ventilation alarm limit
Used to calculate the delay time before
an alarm is generated after the alarm
condition occurs
Determines if the SPT alarm is
displayed on the local Rnet sensor
Determines if the SAT alarm is
displayed on the local Rnet sensor
Determines if the Compressor Lockout
alarm is displayed on the local Rnet
sensor
Determines if the Condenser Water
Temperature alarm is displayed on the
local Rnet sensor
Determines if the Condensate
Overflow alarm is displayed on the
local Rnet sensor
Determines if the Dirty Filter alarm is
displayed on the local Rnet sensor
Determines if the High Space
RH alarm is displayed on the
local Rnet sensor
See TPI
See TPI
See TPI