APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
SCREEN NAME
POINT NAME
Operating Mode
Fan Operating Mode
Occupancy Status
Occupancy Control
Outside Air
Temperature
SPT
SPT Status
SPT Sensor Status
Condensate Overflow
Cooling Set Point
Heating Set Point
Unit
Maintenance
Set Point Adjustment
Auxiliary Heat Control
Set Point
H
O Economizer
2
Control Set Point
Calculated IAQ/
Ventilation Damper
position
Active Compressor
Stages
SAT
Reset Filter Alarm
Overflow Contact
Occupancy Contact
BAS/Keypad Override
OAT Input
BACnet
Keypad Configuration
Password
System Settings
Network
BACnet Time Master
Clock Set
Override Schedules
Pushbutton Override
Keypad Override
Occupancy
Maintenance
Schedules
Occupancy Contact
BAS on/off
Local Occupancy
Schedules
Local Holiday
Schedules
Schedule
Configuration
Local Override
Schedules
BACnet Occupancy
Schedules
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI
— Third Party Integration
PASSWORD
EDITABLE
LEVEL
Off, Fan Only,Economize,
Cooling, Heating, Cont Fan, Test,
Auto/Continuous/Always On
Always Occupied/Local Schedule/
BACnet Schedule/BAS Keypad/
Occupied Contact/Holiday Schedule/
Override Schedule/Pushbutton
Override/Unoccupied None
Normal/Above Limit/Below
No Password
required
X
X
X
X
X
X
X
X
Inactive/Active Occupied
Inactive/Active Occupied
Inactive/Active Occupied/Active
No Password
required
Inactive/Active Occupied
Inactive/Active Occupied
Inactive/Active Occupied
X
X
User/Admin
Password level
access
X
X
RANGE
DEFAULT
Start Delay, Dehumidify
Unoccupied/Occupied
F
F
Limit/Sensor Failure
Inactive/Connected
Normal/Alarm
F
F
F
F
F
%
0/1/2
F
No/Yes
Closed/Open
Closed/Open
Inactive/Occupied/
Inactive
Unoccupied
N/A / Network
Unoccupied
Disable/Enable
Enable
Disable/Enable
Disable
Disable/Enable
Disable
Disable/Enable
Disable
44
NOTES
Displays unit operating mode
Displays how the fan is configured
to operate
Displays the current occupancy status
Displays the origin of the
occupancy control
Displays OAT (Viewable only if OAT
is a network broadcast)
Displays SPT
Displays the SPT status
Displays the connection status
of the Rnet sensor
Displays the status of the
condensate overflow
Displays the actual set point
being used for cooling control
Displays the actual set point
being used for heating control
Displays the offset values from the Rnet
user set point adjustment that is being
applied to the configured set points
Displays the calculated set point being
used for auxiliary heating control
Displays the calculated set point being
used for economizer control
Displays the ventilation damper
position calculated by the DCV control
Displays the actual number of
compressor stages operating
Displays SAT
Used to reset the filter alarm timer after
the filter has been cleaned or replaced
Displays the state of the condensate
overflow switch contact
Displays the state of the external/
remote occupancy input switch contact
Provides capability to force the
equipment to operate in an
occupied or unoccupied mode
Displays if an OAT value is being
received from the Network
See TPI
Mapping
Changes password
See TPI
See TPI
Changes clock/time setting
Used to display the active and
inactive occupancy control inputs
Used to define which occupancy inputs
are used to determine
occupancy mode.