APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME
POINT NAME
# of Fan Speeds
G Output Type
Compressor Stages
Reversing Valve Type
Leaving Air Auxiliary
Heat Type
Entering Air Water
Economizer Type
2-Position Water
Valve Type
Modulating Water
Valve Type
Ventilation Damper
Type
Damper Actuator Type
Configuration
Humidity Sensor
Factory Dehumidifica-
tion Reheat Coil
Service
Configuration
Occupancy
Input Logic
Condensate Switch
Alarm Delay
Condensate Switch
Alarm State
Minimum Condenser
Water Temperature in
Heating
Maximum Condenser
Water Temperature in
Heating
Minimum Condenser
Water Temperature in
Cooling
Maximum Condenser
Water Temperature in
Cooling
IAQ sensor
minimum input
IAQ sensor
maximum input
IAQ sensor
minimum output
IAQ sensor
maximum output
LEGEND
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ
— Indoor Air Quality
OAT — Outdoor Air Temperature
RH
— Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI
— Third Party Integration
PASSWORD
EDITABLE
LEVEL
X
X
X
X
None/2-Position HW/1 Stage
X
X
X
Normally Closed/Normally Open
X
Normally Closed/Normally Open
X
X
X
Admin Password
level access only
X
X
Occupied Open/Occupied Closed
X
X
Alarm OPEN/Alarm CLOSED
X
X
X
X
X
X
X
X
58
RANGE
DEFAULT
1,2,3
Fan On/Fan Low
Fan On
One Stage/Two Stages
One Stage
O type output/B type output
O type
Electric/Modulating HW
None/2-Position/Modulating
Normally
Closed
Normally
Closed
None/2-Position/DCV
(0-10 volt)/(2-10 volt)
0-10 volt
None/Installed
None/Installed
Occupied
CLOSED
5 - 600 seconds
10 sec
Alarm
CLOSED
25 - 60 F
60 F
65 - 100 F
90 F
30 - 60 F
60 F
85 - 120 F
95 F
0 - 5 ma
5 - 20 ma
20 ma
0 - 9999 ppm
0 ppm
0 - 9999 ppm
2000 ppm
NOTES
Used to set number of
3
fan motor speeds
When set to Fan On, G output is
energized when ever any fan speed
is active (required for ECM and Fan
control board). When set to Fan
Low, output is only energized for
Low Speed
Defines the number of
stages of compression
Determines reversing valve
signal output type
Determines Auxiliary
None
Reheat Coil Type
Determines Entering Air
None
Economizer Coil Type
Determines type of 2-position
water valve used
Determines type of modulating
water valve used
Determines type of ventilation
None
damper control to be used
Used to determine ventilation
damper output signal range
(closed - open)
Set to Installed if humidity
None
sensor is present
Set to Installed if factory-installed
None
dehumidification reheat coil
is present
Used to determine external occu-
pancy switch contact occupied state
Delay before equipment alarms on
high condensate level
Determine Alarm state of
condensate switch input
Determines the minimum
acceptable water loop temperature
to start heating
Determines the maximum
acceptable water loop temperature
to start heating
Determines the minimum
acceptable water loop temperature
to start cooling
Determines the maximum
acceptable water loop temperature
to start cooling
Minimum output current (mA)
4 ma
for IAQ sensor
Maximum output current (mA) for
IAQ sensor
Corresponding value in ppm for
minimum output current
Corresponding value in ppm for
maximum output current