Scroll Compressor Rotation —
certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Turn off power to the unit. Install disconnect tag.
2. Reverse any two of the unit power leads.
3. Reapply power to the unit and verify pressures are correct.
The suction and discharge pressure levels should now move
to their normal start-up levels.
When the compressor is rotating in the wrong direction, the
unit makes more noise and does not provide cooling.
After a few minutes of reverse operation, the scroll com-
pressor internal overload protection will open, thus activating
the unit lockout. This requires a manual reset. To reset, turn the
thermostat on and then off.
NOTE: There is a 5-minute time delay before the compressor
will start.

Unit Start-Up Cooling Mode

1. Adjust the unit thermostat to the warmest position.
Slowly reduce the thermostat position until the compres-
sor activates.
2. Check for cool air delivery at unit grille a few minutes
after the unit has begun to operate.
3. Verify that the compressor is on and that the water flow
rate is correct by measuring pressure drop through the
heat exchanger using P/T plugs. See Table 19. Check the
elevation and cleanliness of the condensate lines; any
dripping could be a sign of a blocked line. Be sure the
condensate trap includes a water seal.
Table 20 — Typical 50PTH,PTV,PTD026 Unit Operating Pressures and Temperatures
ENTERING
WATER
WATER
Suction
FLOW
TEMP (F)
Pressure
(Gpm/Ton)
(EWT)
(psig)
1.5
118-128
30
2.25
118-128
3
118-128
1.5
128-138
50
2.25
128-138
3
128-138
1.5
136-146
70
2.25
136-146
3
136-146
1.5
139-149
90
2.25
139-149
3
139-149
1.5
143-153
110
2.25
143-153
3
143-153
LEGEND
DB
— Dry Bulb
HWG — Hot Water Generator
— No heating operation in this temperature range
It is important to be
FULL LOAD COOLING WITHOUT HWG ACTIVE
Discharge
Super-
Sub-
Pressure
heat
cooling
(psig)
(F)
(F)
159-179
25-30
9-14
146-166
25-30
7-12
132-152
25-30
7-12
186-206
18-23
8-13
172-192
18-23
6-11
158-178
18-23
6-11
281-301
7-12
7-12
267-287
7-12
5-10
253-273
7-12
4- 9
368-388
6-11
7-12
354-374
6-11
5-10
340-360
6-11
5-10
465-485
6-11
7-12
450-470
6-11
5-10
433-453
6-11
5-10
4. Check the temperature of both supply and discharge
water. Compare to Tables 20-23. If temperature is within
range, proceed. If temperature is outside the range, check
the cooling refrigerant pressures in Tables 20-23.
5. Check air temperature drop across the coil when com-
pressor is operating. Air temperature drop should be
between 15 and 25 F.

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the
cooling cycle. Allow 5 minutes between tests for the pressure
or reversing valve to equalize.
1. Turn thermostat to lowest setting and set thermostat
switch to HEAT position.
2. Slowly turn the thermostat to a higher temperature until
the compressor activates.
3. Check for warm air delivery at the unit grille within a few
minutes after the unit has begun to operate.
4. Check the temperature of both supply and discharge
water. Compare to Tables 20-23. If temperature is within
range, proceed. If temperature is outside the range, check
the heating refrigerant pressures in Tables 20-23.
5. Once the unit has begun to run, check for warm air deliv-
ery at the unit grille.
6. Check air temperature rise across the coil when compres-
sor is operating. Air temperature rise should be between
20 and 30 F after 15 minutes at load.
7. Check for vibration, noise and water leaks.
Table 19 — Water Temperature Change
Through Heat Exchanger
WATER FLOW RATE (GPM)
For Closed Loop: Ground Source or
Cooling/Boiler Systems at 3 gpm/ton
For Open Loop: Ground Water Systems at
1.5 gpm/ton
FULL LOAD HEATING WITHOUT HWG ACTIVE
Water
Air
Suction
Discharge
Temp
Temp
Pressure
Rise
Drop (F)
(psig)
(F)
DB
16.7-18.7
19-25
73- 83
12.3-14.3
20-26
75- 85
7.9- 9.9
20-26
78- 88
16.3-18.3
19-25
102-112
12.1-14.1
20-26
106-116
7.8- 9.8
20-26
110-120
15.7-17.7
19-25
128-138
11.6-13.6
19-25
134-144
7.6- 9.6
19-25
141-151
14.9-16.9
18-24
162-172
11.0-13.0
18-24
166-176
7.2- 9.2
18-24
171-181
13.9-15.9
17-23
10.2-12.2
17-23
6.5- 8.5
17-23
34
COOLING
RISE (F)
Min
Max
9
20
Super-
Sub-
Pressure
heat
cooling
(psig)
(F)
(F)
273-293
6-11
3- 8
5.9- 7.9
275-295
6-11
3- 8
4.2- 6.2
277-297
6-11
3- 8
2.7- 4.7
302-322
8-12
6-11
8.9-10.9
303-323
8-12
6-11
6.7- 8.7
305-325
8-12
6-11
4.5- 6.5
330-350
10-15
8-13
11.3-13.3
332-352
10-15
8-13
8.5-10.5
334-354
10-15
8-13
5.8- 7.8
367-387
14-19
10-15
14.4-16.4
372-392
15-20
10-15
10.8-12.8
377-397
17-22
10-15
7.1- 9.1
HEATING
DROP (F)
Min
Max
12
4
8
26
10
17
Water
Air
Temp
Temp
Drop
Rise (F)
(F)
DB
16-22
17-23
18-24
22-28
23-29
23-29
27-34
28-35
28-35
33-41
34-42
34-42

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents