Yoshitake DP-200 Series Manual page 11

Table of Contents

Advertisement

1.
When installing the product with the coil set sideways, make sure that the differential pressure (the
minimum differential pressure to operate the valve) between the inlet and the outlet is 0.1 MPa or
more (see Table 1 on Page 1).
* Failure to follow this notice may result in an abnormal operation.
2.
Though the product can be installed at any angle between vertical and horizontal, it cannot be
installed upside-down (see Table 1 on Page 1).
* Failure to follow this notice may result in an abnormal operation.
3.
Before connecting piping to the product, remove foreign substances and dirt inside the piping.
* Failure to follow this notice may keep the product from functioning properly.
4.
When installation, check the direction of the product so that the fluid flowing and the arrow marked
on the product are in the same direction.
* Failure to follow this notice may keep the product from functioning properly (the valve cannot
close).
5.
Make sure to connect a strainer (80–100 mesh) to the inlet of the product.
* Failure to follow this notice may keep the product from functioning properly.
6.
Do not apply excessive load, torque or vibration to the product.
* Failure to follow this notice may result in drastically shortened service life.
7.
Secure enough space required for disassembly or removal of the product at maintenance or
inspections.
* Failure to follow this notice hampers maintenance and inspections.
 Minimum space for disassembly or removal
Model: DP-200 ・ 200F
Nominal size
10-25A
32-50A
L1: Required space for removal/disassembly of the coil
L2, L3, L4: Required space for replacement of the product
8.
If the product is used outdoors, place protective covers or guards above the product in order to avoid
exposure to water.
* Failure to follow this notice may cause an electric leakage.
9.
Do not apply insulation to the solenoid coil.
* Failure to follow this notice may cause the coil burn out with abnormal temperature rise, which
causes malfunction of the product.
10. When the product is used in a facility which cannot stop operating, install a bypass line with a
bypass stop valve.
*Use the bypass line while troubleshooting or disassembling the product so that the facility can keep
operating.
Caution
L1
L2,L3,L4
200
150
250
200
10
(mm)
L3
L4
■ EPDT-266c ■