Xinje XP-18 Series Operating Manual page 41

Integral industrial controller
Table of Contents

Advertisement

Profile dimension
MA-8AD-A/V
Item
Analog input range
Maximum input range
Digital output range
Resolution
Integrated precision
Conversion speed
Power supply for analog
Installation
Profile dimension
MA-4AD
Item
Analog input type
Analog input range
Maximum input range
Digital output range
Resolution
PID output range
Integrated precision
Converting speed
Power for analog
Installation
Profile dimension
MA-4AD2DA
Item
Analog input range
Max input range
Analog output range
63mm×102mm×73.3mm
Voltage
DC0~5V、0~10V
(
exterior
2K ~1M )
±18V
12 bits binary numbers
1/4095(12Bit)
0.8%
20ms per channel
DC24V±10%,100mA
Use M3 screw or fix on DIN46277 rail ( width 35mm )
63mm×102mm×73.3mm
Voltage input
0~5V,0~10V
DC±18V
12 bits binary value (0~4095)
Fix up the module with M3 screw or put on DIN46277 rail (width 35mm)
Analog input ( 4AD )
Voltage input
Current input
0~5V,0~10V
0~20mA,4~20mA
DC±18V
0~40mA
-
Current
DC0~20mA、4~20mA
load
resistor
( exterior load resistor less than
500 )
0~40mA
Analog input (4AD)
Current input
0~20mA,4~20mA
0~40mA
1/4095(12Bit)
0~K4095
0.8%
20ms per channel
DC24V±10%,100mA
63mm×102mm×73.3mm
Analog output ( 2DA )
Voltage output
0~5V、0~10V,
( exterior load
resistor 2K ~1M )
Current output
-
-
0~20mA、4~20mA
(exterior load resistor
less than 500 )
43