Xinje XP-18 Series Operating Manual page 16

Integral industrial controller
Table of Contents

Advertisement

l
Input points
Connect input point and com point with non-voltage point or NPN open collector transistor to
turn on the input.
l
Input loop
The first loop and the second loop are insulated by optical coupler, the second loop has C-R
filter which can prevent wrong action caused by industry noise or input points oscillation. As
the result, there will be a response delay for 10ms to the input points. There is digital filter in
the input points.
l
Input sensitivity
Input current is DC 24V 7mA. To make the input reliable, the ON current should be above
3.5mA, the OFF current should be below 1.5mA.
Typical connection
18

Advertisement

Table of Contents
loading

Table of Contents