Expanded Decision-Makerr 1 Controller - Kohler 20-2250 kW Operation

Industrial generator sets
Table of Contents

Advertisement

1.3 Expanded Decision-Makerr 1 Controller

For identification of the expanded controller's indicators
and controls and their functions, refer to Figure 1-12.
1. Frequency meter
2. AC voltmeter
3. AC ammeter
4. Scale lamps (upper/lower)
5. Selector switch
6. Hourmeter
7. Generator set master switch
Figure 1-12 Expanded Decision-Makerr1 Controller
Figure 1-13 and Figure 1-14 describe the controls and
indicators located on the controller.
Item
Description
AC ammeter
Meter displays the AC output amperage.
Use the selector switch to choose the phase
currents.
AC voltmeter
Meter displays the AC output voltage. Use
the selector switch to choose the output lead
circuits.
DC voltmeter
Meter displays the voltage of the starting
battery(ies).
Fault lamp
Lamp illuminates during engine shutdown if
the engine shuts down because of one of the
following faults: high engine temperature, low
water level, low oil pressure, overcrank, or
overspeed. See Section 2.4.3, Fault
Shutdowns, for additional shutdown
information.
Frequency meter
Meter displays the frequency (Hz) of the
generator set output.
Generator set
Switch functions as the controller reset and
master switch
generator set operation switch.
Figure 1-13 Controls and Indicators
16
Section 1 Specifications and Features
1
2
13
12
11
3
4
10
9
8
8. Voltage adjustment control
9. Fault lamp
10. 10-amp controller fuse
11. DC voltmeter
12. Water temperature gauge
13. Oil pressure gauge
Item
Hourmeter
Oil pressure gauge
Scale lamps
(upper/lower)
Selector switch
Voltage adjustment
control
Water temperature
gauge
10-amp controller
fuse
Figure 1-14 Controls and Indicators, continued
5
7
6
Description
Hourmeter records the generator set total
operating hours for reference in
maintenance scheduling.
Gauge displays the engine oil pressure.
Lamps indicate which AC voltmeter
and/or ammeter scales to read.
Switch selects the generator set output
circuits to measure. When switched to a
position with three circuit labels, the
meters display the amperage on the lead
shown in the upper label and the voltage
between the two leads shown in the
lower label. The AC ammeter and
voltmeter function only with the switch in
the ON position.
Control fine tunes (±5%) the generator
set output voltage.
Gauge displays the engine coolant
temperature.
Fuse protects the controller circuitry from
short circuits and overloads.