6.1.3
Controller (Customer) Connection
Kit (DEC 3+)
The controller connection kit allows easy connection of
controller accessories without accessing the controller
terminal strip. The kit uses a 165-cm (65-in.) wiring
harness to link the controller terminal strip(s) with a
remote terminal strip located in the generator set
Figure 6-6 Controller (Customer) Connection Kit
6.1.4
Engine Prealarm Senders for
NFPA 110 (DEC 3+)
Alert the user of low water temperature, approaching
low oil pressure, and approaching high engine
temperature. Kits for gas-fueled models include a low
fuel pressure switch.
TP-6161
1/12
CONTROLLER CONNECTION KIT MOUNTED IN JUNCTION BOX
junction box. With the exception of a few terminals the
remote terminal strip is identical to that of the controller.
Connect all accessories (except the emergency stop kit)
to the controller connection kit terminal strips. See
Figure 6-6.
See Section 6.2, Accessory and Prime
Power Terminal Strip Connections, for terminal
identification.