Decision-Maker 1 Controller Operation; Controls And Indicators; Starting The Generator Set; Stopping The Generator Set - Kohler 8.5RMY Operation And Installation Manual

Residential/commercial generator sets
Hide thumbs Also See for 8.5RMY:
Table of Contents

Advertisement

2.3 Decision-Maker 1 Controller
Operation
For identification of the Decision-Makert 1 controller's
indicators and controls and their functions, refer to
Figure 2-1.
1
R
RESET/
RUN
OFF
AUTO
6
F1 10 AMP
F2 10 AMP
TYPE ABC
TYPE ABC
5
1. Hourmeter
2. AC circuit breaker
3. Fault lamp
4. Voltage regulator fuse
5. 10-amp controller fuse
6. Generator set master switch
Figure 2-1 Decision-Makert 1 Controller (with Fault
Lamp)
2.3.1

Controls and Indicators

The table in Figure 2-2 describes the controls and
indicators located on the controller.
2.3.2

Starting the Generator Set

The following procedures describe the actions required
to start the generator set.
Local Starting. Move the generator set to the RUN
position to immediately start the generator set.
Auto (Automatic) Starting. Move the generator set
master switch to the AUTO position to allow startup by
the ATS or the remote start/stop switch (connected to
controller terminals TB1-3 and TB1-4).
6
Section 2 Operation
2
ON
3
OFF
FAULT
GM10615
4
Note: The controller provides up to 30 seconds of cyclic
cranking before the overcrank shutdown occurs.
Name
Description
Generator set master
Switch functions as the controller reset
switch
and generator set operation switch.
Hourmeter
Hourmeter records the generator set
total operating hours for reference in
maintenance scheduling.
Voltage regulator fuse,
Fuse protects the voltage regulator
10-amp
circuitry.
Controller fuse, 10-amp
Fuse protects the controller circuitry
from short circuits and overloads.
AC circuit breaker
Circuit breaker trips when a fault is
detected in the AC output circuit.
Fault lamp
Lamp lights when a fault shuts the
generator set down and remains lit until
the generator set master switch is
moved to the OFF/RESET position.
See Section 2.3.4 for fault shutdown
information.
Figure 2-2 Decision-Makert 1 Controls and
Indicators
2.3.3

Stopping the Generator Set

The following procedures describe the actions required
to stop the generator set.
Automatic Stopping
1. The ATS or other device disconnects the load from
the generator set.
2. The generator set continues to run for a preset
cooldown time if the ATS is equipped with an
engine cooldown time delay.
3. The ATS or other device opens the connection
between controller terminals TB1-3 and TB1-4.
The generator set shuts down if the generator set
master switch is in the AUTO position.
Local Stopping
1. Cooldown. Run the generator set at no load for at
least 2 minutes to ensure adequate engine
cooldown.
2. Stopping. Move the generator set master switch
to the OFF/RESET position. The engine stops.
TP-6049 9/02